Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2018008
Status: Active
Facility Name: Jacob's Gas, Inc.
Address: 1005 Golf Rd. Waukegan, IL 60085
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: BB000818
Green Tag Issue Date: 3/12/2026
Green Tag Expire Date: 12/31/2028
MFD Type: Self Service

Owner Details

Owner Name: Jacob's Gas, Inc.
Owner Address: 1005 Golf Road Waukegan, IL 60087
Owner Status: Current Owner
Purchase Date: 3/10/2006
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/12/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0032965 Jacob's Gas, Inc. Current Owner 3/10/2006
U0027588 Akka Enterprises Former Owner 4/1/1994
U0011329 Olson Oil Company, Inc. Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020262276 (Pending)    Issue Date: 9/23/2026    Expiration Date: 11/22/2026    View NOV Form

Tanks Violations
1, 2 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Test expired on 08/15/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector STP
1 Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Test expired on 08/15/2026 for equipment: Overfill Prev Device - Overfill Drop Tube Valve
1 Tank precision test required. - Tank monitor in alarm T1 (Premium): High water alarm T1 (Premium): High water warning ATG inventory shows 262 gallons (7.01") of water in premium tank.
1 Triennial spill prevention equipment testing not completed. - Test expired on 08/15/2026 for equipment: Spill Contain Device - Single Wall Spill Bucket

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-1567 Returned 10/29/2003 11/7/2003 $Not Selected
03-1567 Eligible 11/14/2003 11/24/2003 $10,000
03-1567 Returned 9/14/2006 9/25/2006 $Not Selected
03-1567 Eligible 9/16/2010 11/8/2010 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/16/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 1/1/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/15/2023 8/15/2026
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Lining Materials Internal 9/19/2024 9/19/2029
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/10/2026 3/10/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/10/2026 3/10/2027
Overfill Prev Device Overfill Drop Tube Valve 8/15/2023 8/15/2026
Piping Flexible Double Wall Total Containment Omniflex I Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 8/15/2023 8/15/2026
Tank Steel Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 3/10/2026
Tank Steel Single Wall Precision Test (Tank) Pass 3/10/2026



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/16/1986 Abandoned Material:
Current Age: 45 Abandoned Date:
Install Date: 1/1/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/15/2023 8/15/2026
Corrosion Prot - Piping Flexible Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Lining Materials Internal 9/19/2024 9/19/2029
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/10/2026 3/10/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 3/10/2026 3/10/2027
Overfill Prev Device Overfill Drop Tube Valve 2/6/2024 2/6/2027
Piping Flexible Double Wall Total Containment Omniflex I Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Double Wall Spill Bucket 2/6/2024 2/6/2027
Tank Steel Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Total Containment Omniflex I Precision Test (Piping) Pass 3/10/2026
Tank Steel Single Wall Precision Test (Tank) Pass 9/20/2024

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms