Notice of Violations (Current)
NOV Number:
E0020262276
(Pending)
Issue Date:
9/23/2026
Expiration Date:
11/22/2026
View NOV Form
| Tanks |
Violations |
| 1, 2 |
Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Test expired on 08/15/2026 for equipment: Corrosion Prot - Piping - Sacrificial Anode Flex Connector STP |
| 1 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Test expired on 08/15/2026 for equipment: Overfill Prev Device - Overfill Drop Tube Valve |
| 1 |
Tank precision test required. - Tank monitor in alarm
T1 (Premium): High water alarm
T1 (Premium): High water warning
ATG inventory shows 262 gallons (7.01") of water in premium tank. |
| 1 |
Triennial spill prevention equipment testing not completed. - Test expired on 08/15/2026 for equipment: Spill Contain Device - Single Wall Spill Bucket |