Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2017783
Status: Active
Facility Name: Aurora Packing Company, Inc.
Address: 125 Grant Street
North Aurora, IL 60542
County: Kane
Property Parcel: 15-03-301-020
Facility Type: Private Institution
Owner Type: Private
Green Tag Decal: X004075
Green Tag Issue Date: 4/7/2023
Green Tag Expiration Date: 12/31/2024

Owner Details

Owner Name: Aurora Packing Company, Inc.
Owner Address: 125 Grant Street
North Aurora, IL 60542
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/31/2024

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 10/26/2020 12/31/2022

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0000978 Aurora Packing Company, Inc. Current Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020221780 (Referred to Legal)    Issue Date: 6/6/2022    Expiration Date: 8/5/2022    View NOV Form

Tanks Deficiency
1, 2, 3 Perform a site assessment - Tanks 1, 2 & 3 were removed on 11/30/21. Per Il. Adm. Code 176.330, a site assessment must be conducted at time of removal by a supervising Licensed Professional Engineer (PE) or Professional Geologist (PG). Within 45 days after receipt of lab results from the full site assessment, a “Site Assessment Results” form along with the analytical data must be submitted electronically to the OSFM by the supervising PE or PG. The form can be obtained at: https://webapps.sfm.illinois.gov/USTPortal/Forms/SiteAssessmentResults.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2021-1059 11/30/2021 Removal Log 01341-2021REM

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/30/2021
OSFM First Notify Date: 4/15/1987 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 6/19/2018 6/19/2023
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/2/2020 11/2/2021
Overfill Prev Device Overfill Drop Tube Valve 11/2/2020 11/2/2023
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/2/2020 11/2/2023
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 12000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/30/2021
OSFM First Notify Date: 4/15/1987 Abandoned Material:
Current Age: 22 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 6/19/2018 6/19/2023
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/2/2020 11/2/2021
Overfill Prev Device Overfill Drop Tube Valve 11/2/2020 11/2/2023
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/2/2020 11/2/2023
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 2000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/30/2021
OSFM First Notify Date: 4/15/1987 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal 6/19/2018 6/19/2023
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 11/2/2020 11/2/2021
Overfill Prev Device Overfill Drop Tube Valve 1/4/2021 1/4/2024
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 11/2/2020 11/2/2023
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 2000 Petroleum Use: Back-up Generator
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/15/1987 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 4/1/1984 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 4/27/2023 4/27/2024
Corrosion Prot - Tank Impressed Current Cathodic Protection 4/27/2023 4/27/2024
Leak Detect - Piping European with No Test Req Suction N/A N/A
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 5/15/2024 5/15/2025
Overfill Prev Device Overfill Alarm 4/27/2023 4/27/2026
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 10/14/2022 10/14/2025
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Steel Single Wall Precision Test (Tank) Pass 10/14/2022



Tank Number 5

Capacity: 500 Petroleum Use: None
Product: Used Oil CERCLA Substance:
Status: Aboveground CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 4/15/1987 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID DSL 1

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID DSL 2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID GAS 3

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found