Notice of Violations (Current)
NOV Number:
E0020250230
(Pending)
Issue Date:
1/29/2025
Expiration Date:
3/30/2025
View NOV Form
Tanks |
Violation |
4, 5 |
Sacrificial system failed test; must repair. - 12-19-24 tanks failed the CP test - Must have retested with passing results before this NOV expires
Contractor stated: The results of the remote cell testing indicated that the 10000-gallon stip3 (premium) and 12000-gallon stip3 (regular) tanks are electrically shorted to their associated Fill and ATG risers. The extra risers on the premium tanks is also inconclusively isolated indicating it may also be shorted. |