Notice of Violatlions (Current)
NOV Number:
E0020252791
(Pending)
Issue Date:
10/21/2025
Expiration Date:
12/20/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Dispensers 9/10 and 11/12 need warning signs.
175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers” |
| Facility |
Fire Extinguishers - Past due for annual testing - Fire extinguishers shall be provided in accordance with 41 IL Adm. Code 174.350. |
NOV Number:
E0020252792
(Pending)
Issue Date:
10/21/2025
Expiration Date:
12/20/2025
View NOV Form
| Tanks |
Violations |
| 1 |
Dispensers - hoses cracked, split or worn and require replacement - Main hose is breaking down and has bubbles at botton bend. Replace hose. |
| 1, 2, 3 |
Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed, or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps. |