Notice of Violatlions (Current)
NOV Number:
E0020252902
(Pending)
Issue Date:
10/30/2025
Expiration Date:
12/29/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom. |
NOV Number:
E0020252903
(Pending)
Issue Date:
10/30/2025
Expiration Date:
12/29/2025
View NOV Form
| Tanks |
Violations |
| 5, 6, 7 |
Dispensers - hoses cracked, split or worn and require replacement - Replace main hose. |
| 5, 6, 7 |
Miscellaneous - Vapor caps broken or missing. |
| 5, 6, 7, 8 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to
the environment when the transfer hose is detached from the fill
pipe (e.g., a spill catch basin). Spill containment equipment shall