Notice of Violatlions (Current)
NOV Number:
E0020260920
(Pending)
Issue Date:
4/7/2026
Expiration Date:
6/6/2026
View NOV Form
| Tanks |
Violations |
| 12, 13 |
Line interstitial sensors have been raised and rendered inoperational. - PLEASE REMOVE ALL THE WATER UNDER DISPENSER 3/4 AND REPLACE THE SENSOR BACK TO THE BOTTOM OF THE CONTAINMENT |
| Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
| 12, 13, 14 |
Precision tank test required. |
| 12, 13, 14 |
Required monthly tank interstitial sensor records not available. |
| 12, 13, 14 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - ALL FULL OF WATER |
NOV Number:
E0020260942
(Pending)
Issue Date:
4/7/2026
Expiration Date:
6/6/2026
View NOV Form
| Tanks |
Violations |
| Facility |
Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters |
| Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - PLEASE REPLACE MISSING INTERCOM |
| Facility |
Miscellaneous - PLEASE PLACE A SIGN BY THE SAFETY SHUT OFF SWITCH |