Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2016468
Status: Active
Facility Name: One Stop Union 76, Inc.
Address: 503 Hill Avenue Aurora, IL 60505
County: Kane
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002403
Green Tag Issue Date: 1/10/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: One Stop Citgo of Aurora, Inc.
Owner Address: 503 Hill Avenue Aurora, IL 60505
Owner Status: Current Owner
Purchase Date: 7/1/2015
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 8/13/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 9/1/2022 12/31/2024

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0038798 One Stop Citgo of Aurora, Inc. Current Owner 7/1/2015
U0011348 Alphonsus & Genevieve Olieh Former Owner 12/31/1988
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251287 (Pending)    Issue Date: 5/16/2025    Expiration Date: 7/15/2025    View NOV Form

Tanks Violations
4, 6 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - TANK 4 STP SUMP LID IS UNSTABLE DUE TO STEEL RING CORRODED. TANK 6 PROBE WELL LID IS BROKEN, STEEL RING IS CORRODED AND UNSTABLE.
4, 5, 6 Dispensers - hoses cracked, split or worn and require replacement
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site.
4, 5, 6, 7 Impressed current system failed test or appears non operational. Must repair. - 175.510 f)1) Corrosion Protection All corrosion protection systems shall be operated and maintained to continuously provide corrosion protection to the metal components of that portion of the tank and piping that routinely contain regulated substances and are in contact with the ground, backfill or water.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site.
4, 5, 6, 7 Monthly impressed current system log not available or maintained. - 175.510 f)4)c) Impressed current systems must be inspected every 30 days and reports or a log maintained that shows date of inspection, initials of inspector, hour, volt and amp readings, and power on verification. A minimum of 2 years of records shall be kept on site. Impressed Current Logs can be found at https://sfm.illinois.gov/

NOV Number: E0020251303 (Pending)    Issue Date: 5/16/2025    Expiration Date: 7/15/2025    View NOV Form

Tanks Violations
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - All dispensers are required to have attended self service signs. 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers”

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 01/01/1988 - REM
2 6000 Gasoline Removed Federal $0.00 01/01/1988 - REM
3 6000 Gasoline Removed Federal $0.00 01/01/1988 - REM
4 10000 Gasoline - Regular Currently in use Federal $0.00
5 8000 Gasoline - Premium Currently in use Federal $0.00
6 8000 Gasoline - Mid-grade Currently in use Federal $0.00
7 6000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found