Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2016445
Status: Active
Facility Name: Express Lane Shell
Address: 302 East Grant Street Marengo, IL 60152
County: McHenry
Property Parcel: 11-36-301-001
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001697
Green Tag Issue Date: 5/3/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Arthur J. Johnson Family Limited Partnership
Owner Address: 1305 12th Avenue Rock Falls, IL 61071
Owner Status: Current Owner
Purchase Date: 1/1/2010
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 9/22/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/3/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040750 Arthur J. Johnson Family Limited Partnership Current Owner 1/1/2010
U0020947 Shell Oil Co Former Owner 8/3/1993
U0000651 B.A.P.A., LLC & PT, LLC Former Owner 12/31/1967
U0008040 Johnson Oil Company Former Owner
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner
U0027449 Equilon Enterprises, LLC Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020251571 (Pending)    Issue Date: 6/23/2025    Expiration Date: 8/22/2025    View NOV Form

Tanks Violations
9, 10 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. Tank 9 regular STP lid is out of round and would not come up. Tank 10 premium STP lid handles are broken off, and the ATG lid is out of round and will not come up.
9 Submit Notification Form for Product Change - Submit OSFM Notification Form showing change in product from midgrade to regular.
8, 9, 10 Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - Under dispenser containment sumps 5/6 & 11/12 contain liquid which is corroding the exposed steel. Install approved cathodic protection to prevent further corrosion of dispenser piping and related piping components.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
04-1272 9/8/2004 Removal Log 04885-2004REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
04-1272 Eligible 6/29/2005 7/14/2005 $15,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal $0.00 09/20/1989 - REM
2 8000 Gasoline Removed Federal $0.00 09/20/1989 - REM
3 6000 Gasoline Removed Federal $0.00 09/20/1989 - REM
4 500 Used Oil Removed Federal $0.00 09/20/1989 - REM
5 12000 Gasoline Removed Federal $0.00 09/08/2004 - REM
6 12000 Gasoline Removed Federal $0.00 09/08/2004 - REM
7 12000 Gasoline Removed Federal $0.00 09/08/2004 - REM
8 15000 Gasoline - Regular Currently in use Federal $0.00
9 6000 Gasoline - Regular Currently in use Federal $0.00
10 6000 Gasoline - Premium Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms