A/B operator retraining required as a result of issuance of the Notice of Violation - Must provide new A/B certificate after course completed |
Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
Facility |
Facility Operation and Maintenance Plan not updated to new requirements. - Needs updating |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; The form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. |
Facility |
Missing list of designated Class A/B & C Operators - Include copies of all certificates |
1, 2, 3 |
Monthly line interstitial sensor records not available. - Maintain one NORMAL report per LINE, per month, from ATG. Must maintain 24 months’ worth |
1, 2, 3 |
Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth. |
1, 2, 3 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |
1, 2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2, 3 |
Tank precision test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “PASS” from ATG. |