Notice of Violations (Current)
NOV Number:
E0020250483
(Pending)
Issue Date:
2/26/2025
Expiration Date:
4/27/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020250484
(Pending)
Issue Date:
2/26/2025
Expiration Date:
4/27/2025
View NOV Form
Tanks |
Violation |
6, 7, 8 |
Piping interstitial must be open in all sumps - Product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b) (All Dispensers and STPs) |
6, 7, 8 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Remove liquid/debris and maintain clean and dry at all times. |
7, 8 |
Verify and test piping sump sensor for positive shutdown - For installations and replacements after September 1, 2010, these sensors must immediately shut off the submersible turbine pump (STP) supplying that line upon detection of a release. Reference 175.640 a)1) (Diesel and Premium STP sensors due to like for like replacements in 2016 and 2021) |