Notice of Violations (Current)
NOV Number:
E0020250361
(Pending)
Issue Date:
2/11/2025
Expiration Date:
4/12/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
Facility |
Fire Extinguishers - Past due for annual testing - Were due March 2023 |
Facility |
LP gas storage lacks proper collision protection or a 40" measurement from cabinet to a 5" raised sidewalk - Provide appropriate collision protection for LP tank cage. Refer to OSFM Rules section 175.210 q) for proper placement of collision protection. |
NOV Number:
E0020250362
(Pending)
Issue Date:
2/11/2025
Expiration Date:
4/12/2025
View NOV Form
Tanks |
Violation |
Facility |
Facility Operation and Maintenance Plan not completed or available. - Fill out completely. |
6, 7, 8 |
Line interstitial sensors have been raised and rendered inoperational. - STPs |
8 |
Miscellaneous - Equipment in disrepair 176.410 |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov. |
6, 7, 8 |
Piping interstitial must be open in all sumps - Product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b) (STPs and All Disp.) |