Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2014571
Status: Active
Facility Name: Speedway #7514
Address: 1570 Big Timber Road
Elgin, IL 60123
County: Kane
Property Parcel: 06-03-351-029
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001675
Green Tag Issue Date: 3/31/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500
Springfield, OH 45501
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/4/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner
U0002795 Emro Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01331-2024UPG Upgrade Approved / Issued 10/19/2024 10/21/2024 4/22/2025 Documents

Notice of Violations (Current)

NOV Number: E0020250699 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
12, 13, 14 Dispensers - hoses cracked, split or worn and require replacement - Replace main hose(s) on the above listed dispenser(s).
12, 13, 14 Piping interstitial must be open in all sumps - Remove all jumper tubing/pull back test boots for piping interstitial. 175.420 b. DISPENSER 1/2 & 5/6, AND ALL STP'S.

NOV Number: E0020250701 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
04-1381 10/4/2004 Removal Log 05119-2004REM
91-0495 8/11/1992 Removal Log 5126-92
99-0227 2/2/1999 Removal Log 4781-98

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-1695 Eligible 5/10/1996 5/23/1996 $10,000
91-0495 Eligible 11/8/1996 12/24/1996 $10,000
04-1381 Eligible 11/15/2005 12/22/2005 $10,000
89-0646 Eligible 11/8/2007 11/20/2007 $50,000
99-0227 Eligible 11/8/2007 11/20/2007 $10,000
91-0004 Eligible 11/8/2007 11/20/2007 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/4/2004
OSFM First Notify Date: 12/29/1992 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 8/14/1992 Red Tag Issue Date:
Last Used Date: 10/1/2004 Fee Due: $0.00
Product Date: 9/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/4/2004
OSFM First Notify Date: 12/29/1992 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 8/14/1992 Red Tag Issue Date:
Last Used Date: 10/1/2004 Fee Due: $0.00
Product Date: 9/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/4/2004
OSFM First Notify Date: 12/29/1992 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 8/14/1992 Red Tag Issue Date:
Last Used Date: 10/1/2004 Fee Due: $0.00
Product Date: 9/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/4/2004
OSFM First Notify Date: 12/29/1992 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 8/14/1992 Red Tag Issue Date:
Last Used Date: 10/1/2004 Fee Due: $0.00
Product Date: 9/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/4/2004
OSFM First Notify Date: 12/29/1992 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 8/14/1992 Red Tag Issue Date:
Last Used Date: 10/1/2004 Fee Due: $0.00
Product Date: 9/1/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/11/1992
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 1/1/1981 Red Tag Issue Date:
Last Used Date: 8/1/1992 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/11/1992
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 8/1/1992 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/11/1992
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/11/1992
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/11/1992
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 21 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 8/1/1992 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 11

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 2/2/1999
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 12/31/1974 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 12

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/2/2004 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 10/12/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/12/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/15/2024 11/15/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/15/2024 11/15/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/15/2024 11/15/2025
Overfill Prev Device Overfill Drop Tube Valve 12/8/2022 12/8/2025
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor 11/15/2024 11/15/2025
Spill Contain Device Single Wall Spill Bucket 9/10/2023 9/10/2026
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 13

Capacity: 20000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/2/2004 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 10/12/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/12/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/15/2024 11/15/2025
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/15/2024 11/15/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/15/2024 11/15/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/15/2024 11/15/2025
Overfill Prev Device Overfill Drop Tube Valve 12/8/2022 12/8/2025
Overfill Prev Device Overfill Drop Tube Valve 12/8/2022 12/8/2025
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor 11/15/2024 11/15/2025
Piping Single Wall STP/Tanktop Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor 11/15/2024 11/15/2025
Spill Contain Device Single Wall Spill Bucket 9/10/2023 9/10/2026
Spill Contain Device Single Wall Spill Bucket 9/10/2023 9/10/2026
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 14

Capacity: 4000 Petroleum Use:
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 12/2/2004 Abandoned Material:
Current Age: 20 Abandoned Date:
Install Date: 10/12/2004 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/12/2004

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Composite Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 11/15/2024 11/15/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 11/15/2024 11/15/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 11/15/2024 11/15/2025
Overfill Prev Device Overfill Drop Tube Valve 12/8/2022 12/8/2025
Piping Flexible Double Wall OPW Pisces N/A N/A
Piping Single Wall STP/Tanktop Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor 11/15/2024 11/15/2025
Spill Contain Device Single Wall Spill Bucket 9/10/2023 9/10/2026
Tank Composite Double Wall Permatank N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 11/15/2024 11/15/2025



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 11/15/2024 11/15/2025



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 11/15/2024 11/15/2025



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/10/2023 9/10/2026
Leak Detect - Piping Sump Sensor with positive shutdown 11/15/2024 11/15/2025

MFD Motorfuel Dispensing Forms

No Forms Found