Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2014566
Status: Active
Facility Name: Speedway #7504
Address: 1902 N. Arlington Heights Rd. Arlington Heights, IL 60004
County: Cook
Property Parcel: 03-17-302-032-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002828
Green Tag Issue Date: 2/27/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Speedway, LLC
Owner Address: P.O. Box 1500 Springfield, OH 45501
Owner Status: Current Owner
Purchase Date:
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/18/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0026552 Speedway, LLC Current Owner
U0002795 Emro Marketing Co Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01050-2025UPG Upgrade Cancelled by Contractor 8/12/2025 8/12/2025 2/13/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251910 (Pending)    Issue Date: 7/29/2025    Expiration Date: 9/27/2025    View NOV Form

Tanks Violations
3 Precision line test required. - Tanknology failed a precision line test due to leaks in piping. Piping needs to be repaired and another precision line test is required. Passing results shall be entered on OSFM portal.

NOV Number: E0020251941 (Pending)    Issue Date: 7/31/2025    Expiration Date: 9/29/2025    View NOV Form

Tanks Violations
3 Line interstitial sensors have been raised and rendered inoperational. - 175.640 a) 2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
3 Miscellaneous - Piping has a slight leak and there 7" inches of product in sump. Repair piping and remove product.
2 Open electrical conduit or junction boxes. - Conduit is broken under junction box in sensor well next to premium vapor well.
3 Precision line test required. - Tank #3 failed precision line test. Repair shall be made and another precision line test required with passing results entered into OSFM portal.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.
1 Stick inserted in drop tube overfill device rendering it inoperative - Remove stick. - Remove stick.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
91-2203 10/17/1994 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 15000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/15/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 10/21/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/21/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 2/16/2024 2/16/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/1/2025 5/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 5/1/2025 5/1/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/1/2025 5/1/2026
Overfill Prev Device Overfill Drop Tube Valve 6/14/2023 6/14/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 7/22/2024 7/22/2027
Leak Detect - Piping Sump Sensor 5/1/2025 5/1/2026
Spill Contain Device Single Wall Spill Bucket 7/22/2024 7/22/2027
Tank STIP3 Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/15/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 10/21/1994 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 10/21/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 2/16/2024 2/16/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/1/2025 5/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 5/1/2025 5/1/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/1/2025 5/1/2026
Overfill Prev Device Overfill Drop Tube Valve 5/10/2023 5/10/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 7/22/2024 7/22/2027
Leak Detect - Piping Sump Sensor 5/1/2025 5/1/2026
Spill Contain Device Single Wall Spill Bucket 7/22/2024 7/22/2027
Tank STIP3 Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 4000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 3/15/1996 Abandoned Material:
Current Age: 30 Abandoned Date:
Install Date: 10/21/1994 Red Tag Issue Date: 7/29/2025
Last Used Date: Fee Due: $0.00
Product Date: 10/21/1994

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Flexible Non-Corrosive N/A N/A
Corrosion Prot - Tank Sacrificial Anode Cathodic Protection 2/16/2024 2/16/2027
Leak Detect - Piping Electronic Pressurized Line Leak Detection 5/1/2025 5/1/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 5/1/2025 5/1/2026
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 5/1/2025 5/1/2026
Overfill Prev Device Overfill Drop Tube Valve 5/10/2023 5/10/2026
Piping Flexible Double Wall Environ Geo Flex N/A N/A
Piping Single Wall STP/Tanktop Sump 6/6/2025 6/6/2028
Leak Detect - Piping Sump Sensor 5/1/2025 5/1/2026
Spill Contain Device Single Wall Spill Bucket 7/22/2024 7/22/2027
Tank STIP3 Double Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Flexible Double Wall Environ Geo Flex Precision Test (Piping) Fail 7/24/2025



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/17/1994
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1965 Red Tag Issue Date:
Last Used Date: 10/1/1994 Fee Due: $0.00
Product Date: 1/1/1965

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/17/1994
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 29 Abandoned Date:
Install Date: 1/1/1965 Red Tag Issue Date:
Last Used Date: 10/1/1994 Fee Due: $0.00
Product Date: 1/1/1965

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/17/1994
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 1/1/1980 Red Tag Issue Date:
Last Used Date: 10/1/1994 Fee Due: $0.00
Product Date: 1/1/1980

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/17/1994
OSFM First Notify Date: 4/18/1986 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 1/1/1980 Red Tag Issue Date:
Last Used Date: 10/1/1994 Fee Due: $0.00
Product Date: 1/1/1980

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/22/2024 7/22/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/22/2024 7/22/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/22/2024 7/22/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/22/2024 7/22/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/22/2024 7/22/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/22/2024 7/22/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/22/2024 7/22/2027
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found