Notice of Violations (Current)
NOV Number:
E0020250523
(Pending)
Issue Date:
2/28/2025
Expiration Date:
4/29/2025
View NOV Form
Tanks |
Violation |
12 |
Install or replace lockable fill pipe caps. - E-85 snap cap is missing the gasket. Repair/replace. |
Facility |
Miscellaneous - (Emergency stop is Blocked inside) Emergency stop shall be readily accessible to the attendant. |
2, 3, 4 |
Piping interstitial must be open in all sumps - Siphon bar double piping is in a closed position. |
1, 2, 3, 4, 5, 12 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
2, 3, 4 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Needs to be tested due to regulated sensors and upgrade in 2014. (All Regular STP tanks top sumps) |
2, 3, 4 |
Verify and test piping sump sensor for positive shutdown - Need to test STP sump sensor in all regular STPs due to siphon bars and Dispensers 1/2 and 11/12. Need to be positve shut down due to upgrade 2014. |
NOV Number:
E0020250524
(Pending)
Issue Date:
2/28/2025
Expiration Date:
4/29/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |