Notice of Violations (Current)
NOV Number:
E0020250289
(Pending)
Issue Date:
2/4/2025
Expiration Date:
4/5/2025
View NOV Form
Tanks |
Violation |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Minimum signage is not up to code. Reference 175.210 o) |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020250290
(Pending)
Issue Date:
2/4/2025
Expiration Date:
4/5/2025
View NOV Form
Tanks |
Violation |
Facility |
Miscellaneous - Each emergency stop shall be identified by an approved sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. Reference 175.210 d)3) (Out side Emergency Stop) |
7, 8, 19 |
Overfill alarm does not appear to function properly. - Light bulb is not working. |
7, 8, 19 |
Shear valve(s) not properly mounted and/or not at proper height. - Shear valves are to low. |