Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2013823
Status: Active
Facility Name: Your Local Gas, Inc.
Address: 273 W. Main Street
Glenwood, IL 60425
County: Cook
Property Parcel: 32-04-404-031-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002042
Green Tag Issue Date: 1/8/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Your Local Gas, Inc.,
Owner Address: 14112 Pulaski Road
Crestwood, IL 60418
Owner Status: Current Owner
Purchase Date: 3/3/2011
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/3/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/8/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0036141 Your Local Gas, Inc., Current Owner 3/3/2011
U0029668 Krumrie, Dennis Former Owner 2/5/2000
U0009663 Marathon Oil Company Former Owner 12/31/1967
U0012018 Pole Richard A Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251004 (Pending)    Issue Date: 4/14/2025    Expiration Date: 6/13/2025    View NOV Form

Tanks Violation
5, 7 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
5, 6, 7 Annual leak detection certification not completed (Required annually). - (ATG Cert.)
5, 6, 7 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Three-year third-party testing required on sacrificial anode system. Perform testing. (All STPs)
6 Mechanical line leak detector requires annual functional test.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
6 Precision line test required. - Annual line test past due.
5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
5, 6, 7 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
N/A 1/24/2024 Removal Log 00016-2024REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
20240286 Eligible 1/20/2025 1/29/2025 $5,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline Removed Federal 09/01/1986 - REM
2 6000 Gasoline Removed Federal 09/01/1986 - REM
3 8000 Gasoline Removed Federal 09/01/1986 - REM
4 550 Used Oil Removed Federal 09/01/1986 - REM
5 8000 Gasoline - Regular Currently in use Federal $0.00
6 8000 Gasoline - Regular Currently in use Federal $0.00
7 8000 Gasoline - Premium Currently in use Federal $0.00
8 500 Used Oil Removed Federal $0.00 01/24/2024 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active

MFD Motorfuel Dispensing Forms

No Forms Found