Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2013801
Status: Active
Facility Name: SNK Marathon
Address: 10 W. Golf Rd. Des Plaines, IL 60016
County: Cook
Property Parcel: 08-13-202-007-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z000048
Green Tag Issue Date: 7/17/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: 10 W Golf Des Plaines, LLC
Owner Address: 26 Mill Plain Rd. Danbury, CT 06811
Owner Status: Current Owner
Purchase Date: 9/9/2025
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/12/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041651 10 W Golf Des Plaines, LLC Current Owner 9/9/2025
U0040098 S & S Illinois Investments LLC Former Owner 2/8/2021
U0032209 Combined Real Estate, LLC Former Owner / Operator 1/23/2009
U0035252 MPCO Real Estate, LLC Former Owner / Operator 1/23/2009
U0009659 Marathon Petroleum Company LP Former Owner / Operator 12/31/1967
U0026531 DO NOT USE THIS OWNER ID - Casey's General Stores Former Owner / Operator

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020262027 (Pending)    Issue Date: 8/10/2026    Expiration Date: 10/9/2026    View NOV Form

Tanks Violations
1, 3, 4, 10 Annual electronic line leak detector test not completed.
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 3, 4, 10 Annual leak detection certification not completed (Required annually).
1, 3, 4, 10 Line interstitial sensor functional test not accomplished (Required annually).
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training - Copies of all certificates must be kept on site
4 Open electrical conduit or junction boxes. - Under dispenser 9/10
1, 3, 4 Precision line test required.
1, 3, 4, 10 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).
1, 3, 4, 10 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
10 Tank interstitial sensor functional test not accomplished (Required annually).
1, 3, 4, 10 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Under dispenser 13/14. Provide documentation from a contractor of repair

NOV Number: E0020262028 (Pending)    Issue Date: 8/10/2026    Expiration Date: 10/9/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable
Facility Miscellaneous - Each emergency stop shall be identified by a sign stating "EMERGENCY STOP" in 2 inch red capital letters. 175.210.d.3

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2025-0587 8/14/2025 Removal Log 00987-2025REM
22-0251 3/24/2022 Removal Log 00297-2022REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-1270 Eligible 12/28/1993 1/13/1994 $10,000
20220251 Eligible 4/22/2022 4/22/2022 $5,000 Letter
20250587 Eligible 9/23/2025 9/24/2025 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 2/10/2026 2/10/2029
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 8/11/2026 8/11/2027
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 6/26/2025 6/26/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve Not applicable Not applicable
Overfill Prev Device Overfill Drop Tube Valve 6/26/2025 6/26/2028
Piping Fiberglass Single Wall Piping Ameron Not applicable Not applicable
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 6/26/2025 6/26/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/3/2020
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 6/26/2025
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Precision Test (Piping) Pass 6/26/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/31/2022



Tank Number 2

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/24/2022
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/25/2019 7/25/2022
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 2/24/2021 2/24/2022
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 12/3/2020 12/3/2021
Overfill Prev Device Ball Float Vent Valve 12/3/2020 12/3/2023
Piping Fiberglass Single Wall Piping Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 1/28/2021 1/28/2024
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/3/2020



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 3/10/2026 3/10/2029
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 6/26/2025 6/26/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve Not applicable Not applicable
Overfill Prev Device Overfill Drop Tube Valve 6/26/2025 6/26/2028
Piping Fiberglass Single Wall Piping Ameron Not applicable Not applicable
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 6/26/2025 6/26/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/3/2020
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 6/26/2025
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Precision Test (Piping) Pass 6/26/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/31/2022



Tank Number 4

Capacity: 6000 Petroleum Use: None
Product: B-11 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 3/30/2026 3/30/2029
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root EMC with CSLD 6/26/2025 6/26/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve Not applicable Not applicable
Overfill Prev Device Overfill Drop Tube Valve 6/26/2025 6/26/2028
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Not applicable Not applicable
Piping Fiberglass Single Wall Piping Ameron Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 6/26/2025 6/26/2028
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/3/2020
Piping Fiberglass Single Wall Piping Ameron Precision Test (Piping) Pass 6/26/2025
Piping Fiberglass Single Wall Piping Ameron Dualoy 3000/L Precision Test (Piping) Pass 6/26/2025
Tank Fiberglass Single Wall Precision Test (Tank) Pass 3/31/2022



Tank Number 5

Capacity: 550 Petroleum Use: None
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/14/2025
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 1/1/1985 Red Tag Issue Date:
Last Used Date: 5/15/2024 Fee Due: $0.00
Product Date:

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Gravity Feed Not applicable Not applicable
Leak Detect - Tank 110 - 600 gallons Manual Tank Gauging Not applicable Not applicable
Overfill Prev Device Less than 25 gallon fills Not applicable Not applicable
Piping Fiberglass Double Wall Not applicable Not applicable
Piping Not Installed STP/Tanktop Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not applicable Not applicable
Spill Contain Device Single Wall Spill Bucket 12/3/2020 12/3/2023
Tank Fiberglass Single Wall Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Single Wall Precision Test (Tank) Pass 9/6/2022
Leak Detect - Piping Non-Discriminating Sump Sensor Sensor Functional Pass 5/17/2010



Tank Number 6

Capacity: 4000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1985
OSFM First Notify Date: 10/29/1993 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/1/1961 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 7

Capacity: 5000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1985
OSFM First Notify Date: 10/29/1993 Abandoned Material:
Current Age: 24 Abandoned Date:
Install Date: 1/1/1961 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 8

Capacity: 6000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1985
OSFM First Notify Date: 10/29/1993 Abandoned Material:
Current Age: 15 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 9

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/1/1985
OSFM First Notify Date: 10/29/1993 Abandoned Material:
Current Age: 14 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: Fee Due:
Product Date:

Equipment Information

No Equipment Listed


Additional Tests

No Tests Listed




Tank Number 10

Capacity: 8000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/12/2022 Abandoned Material:
Current Age: 4 Abandoned Date:
Install Date: 4/28/2022 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 5/13/2022

Equipment Information

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive Not applicable Not applicable
Corrosion Prot - Tank Fiberglass Non-Corrosive Not applicable Not applicable
Leak Detect - Piping Electronic Pressurized Line Leak Detection 6/26/2025 6/26/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 6/26/2025 6/26/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 6/26/2025 6/26/2026
Overfill Prev Device Overfill Drop Tube Valve 6/26/2025 6/26/2028
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Not applicable Not applicable
Piping Single Wall STP/Tanktop Sump 9/3/2025 9/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 9/3/2025 9/3/2028
Spill Contain Device Single Wall Spill Bucket 6/26/2025 6/26/2028
Tank Fiberglass Double Wall Containment Solutions Not applicable Not applicable

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 6/26/2025
Tank Fiberglass Double Wall Containment Solutions Precision Test (Tank) Pass 5/12/2022

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 11/12

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/3/2025 9/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026



Name\ID 13/14

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/3/2025 9/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026



Name\ID 15/16

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 9/3/2025 9/3/2028
Leak Detect - Piping Sump Sensor with positive shutdown 6/26/2025 6/26/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump Not applicable Not applicable
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Required Not applicable Not applicable

Failed test = the latest test has failed.

Not applicable = a test does not apply to this equipment type or configuration.

No passing test found = a passing test is expected but was not found from the source data.


MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2013801 SNK Marathon Des Plaines 05/13/2022 Letter Form