Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2013381
Status: Active
Facility Name: Braidwood Fuel, Inc.
Address: 1190 W. Kennedy Road Braidwood, IL 60408
County: Will
Property Parcel: 02-24-07-311-002-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001691
Green Tag Issue Date: 8/22/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Sneha Group, Inc.
Owner Address: 1190 West Kennedy Road Braidwood, IL 60408
Owner Status: Current Owner
Purchase Date: 4/18/2018
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 10/12/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/22/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039139 Sneha Group, Inc. Current Owner 4/18/2018
U0038187 Braidwood Oil, Inc. Former Owner 4/1/2015
U0032788 K V Oil Corporation Former Owner 3/30/2005
U0005366 Fox's Marathon Former Owner 6/1/1982
U0014431 Amoco Oil Company Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
01171-2025UPG Upgrade Approved / Issued 9/5/2025 9/5/2025 3/5/2026 Documents
00033-2026CAT Cathodic Protection Approved / Issued 1/7/2026 1/7/2026 7/7/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020253313 (Pending)    Issue Date: 12/19/2025    Expiration Date: 2/17/2026    View NOV Form

Tanks Violations
1, 2, 3 Flex connector sacrificial system failed test - must replace and retest - Failed testing on 12/17/2025.
1, 2, 3 Sacrificial system failed test; must repair. - Failed testing on 12/17/2025.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 7/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 1/17/2023 12/17/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/17/2023 12/17/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/17/2025 12/17/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 with SCALD 12/17/2025 12/17/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 1/17/2023 1/17/2026
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Double Wall Spill Bucket 9/10/2025 9/10/2028
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/17/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/16/2022



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 7/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 1/17/2023 12/17/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/17/2023 12/17/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/17/2025 12/17/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 with SCALD 12/17/2025 12/17/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 1/17/2023 1/17/2026
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 1/17/2023 1/17/2026
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/17/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/16/2022



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 7/1/1985 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1985

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 1/17/2023 12/17/2025
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank STIP3 Cathodic Protection with Dielectric Coating 1/17/2023 12/17/2025
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 12/17/2025 12/17/2026
Leak Detect - Tank Automatic Tank Gauging Incon TS 1001 with SCALD 12/17/2025 12/17/2026
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 1/17/2023 1/17/2026
Piping Flex Connector Steel N/A N/A
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Spill Contain Device Single Wall Spill Bucket 1/17/2023 1/17/2026
Tank STIP3 Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/17/2025
Tank STIP3 Single Wall Precision Test (Tank) Pass 5/16/2022



Tank Number 4

Capacity: 500 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 1/20/1998
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1959 Red Tag Issue Date:
Last Used Date: 1/1/1975 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 500 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Exempt Removed Date: 1/20/1998
OSFM First Notify Date: 4/30/1986 Abandoned Material:
Current Age: 39 Abandoned Date:
Install Date: 1/1/1959 Red Tag Issue Date:
Last Used Date: 1/1/1972 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found