1, 3 |
Install or replace lockable fill pipe caps. - Lockable fill pipe cap is broken and requires replacement. (Per 41 Ill Admin code 175.445(c)) |
1, 2, 3, 4 |
Miscellaneous - Required monthly line leak test records not available. |
1, 2, 3, 4 |
Precision line test required. - Precision line test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.640(a)(4)) |
1, 2, 3, 4 |
Required monthly tank leak test records not available. - Maintain one NORMAL/PASS report per TANK, per month, from tank monitor. (CSLD) |
1, 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
Facility |
Submit Notification Form For Ownership Change - Site manager stated he bought the station.
Submit OSFM Notification Form showing change in facility ownership, complete and submit the online Notification for Underground Storage Tanks form which can be found at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm |
1, 2, 3, 4 |
Tank precision test required. - Precision tank test is required due to missing or failed monthly monitoring (Per 41 Ill Admin code 175.630(c)(2))) |