Notice of Violatlions (Current)
NOV Number:
E0020252026
(Pending)
Issue Date:
8/11/2025
Expiration Date:
10/10/2025
View NOV Form
Tanks |
Violations |
1 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Tank top |
1, 2, 3, 4, 5 |
Impressed current system failed test or appears non operational. Must repair. - Hour meter is not working |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - Missing June & July |
1, 2, 3, 4, 5 |
Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Or repair to prevent water from entering the containment. Between 5/6 & 7/8 |
NOV Number:
E0020252028
(Pending)
Issue Date:
8/11/2025
Expiration Date:
10/10/2025
View NOV Form
Tanks |
Violations |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
Facility |
Miscellaneous - Each emergency stop shall be identified by a sign on all-weather materials stating "EMERGENCY
STOP" in 2 inch red capital letters. 175.210.d.3 |