Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2011882
Status: Active
Facility Name: Brake Time
Address: 150 W. Commercial Drive
Morris, IL 60450
County: Grundy
Property Parcel: 02-33-478-012
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: Y001005
Green Tag Issue Date: 1/22/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Brake Time IL Properties, LLC
Owner Address: 6300 Richmond Avenue, Suite 300
Houston, TX 77057
Owner Status: Current Owner
Purchase Date: 11/6/2024
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 1/9/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/22/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041353 Brake Time IL Properties, LLC Current Owner 11/6/2024
U0039389 Minit Mart, LLC Former Owner 12/5/2018
U0026726 TA Operating, LLC Former Owner 8/13/2015
U0027811 BP of Morris, Inc. Former Owner 6/14/2007
U0015192 Trenter Oil Co Inc Former Owner 12/31/1967
U0010459 MKM Oil, Inc. Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00268-2025UPG Upgrade Approved / Issued 3/6/2025 3/6/2025 9/8/2025 Documents

Notice of Violations (Current)

NOV Number: E0020250079 (Pending)    Issue Date: 1/8/2025    Expiration Date: 3/9/2025    View NOV Form

Tanks Violation
1, 2 Drop tube valve or overfill alarm failed inspection. Repair or replace equipment. - OSFM received an Overfill Prevention Equipment Inspection form from a licensed UST contractor on 12/17/24, declaring tanks 1 & 2 failed their triennial inspection on 11/26/24. You must repair or replace the overfill devices.
Facility Financial responsibility must be reported yearly - Per 176.220, tank owners/operators must submit an electronic Financial Responsibility Report form on an annual basis. Financial Responsibility must be maintained until the tank is removed or properly abandoned in place by a licensed UST decommissiong contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility.
1 Spill prevention equipment failed triennial testing. Must be repaired or replaced. - OSFM received a Containment Sump Testing form from a licensed UST contractor on 12/17/24, declaring tank #1 failed their triennial inspection on 11/26/24. You must repair or replace the spill prevention equipment device.

NOV Number: E0020250553 (Pending)    Issue Date: 3/4/2025    Expiration Date: 5/3/2025    View NOV Form

Tanks Violation
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - Dispenser 6 and 17/18 Need warning signs. Warning signs must be seen from all dispensers. 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers”
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - 175.210 h)The attendant shall at all times be able to communicate with persons in the dispensing area. Repair or replace intercom.

NOV Number: E0020250554 (Pending)    Issue Date: 3/4/2025    Expiration Date: 5/3/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
Facility Facility Operation and Maintenance Plan not completed or available. - Operations and Maintenance Template needs to be updated and kept on site
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site.
1, 2, 3 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2, 3, 8 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
1, 2 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
90-1124 4/26/1990 Removal Log

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 12000 Gasoline - Regular Currently in use Federal $0.00
3 10000 Gasoline - Premium Currently in use Federal $0.00
4 6000 Gasoline Removed Federal $0.00 04/16/1990 - REM
5 6000 Gasoline Removed Federal $0.00 04/26/1990 - REM
6 6000 Gasoline Removed Federal $0.00 04/26/1990 - REM
7 550 Fuel Oil Removed Federal $0.00 04/26/1990 - REM
8 10000 B-11 Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
11/12 Active
13/14 Active
15/16 Active
17/18 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active

MFD Motorfuel Dispensing Forms

No Forms Found