Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0034331 |
AJ Food Shop, Inc. |
Current Owner |
7/15/2007 |
| U0032168 |
John P. John |
Former Owner |
5/1/2003 |
| U0013951 |
Sierra Petroleum Company, Inc. |
Former Owner |
5/1/2003 |
Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
No Applications Found
Tank Number 1
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
40 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1986 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1986 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/13/2023 |
11/13/2026 |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
7/5/2023 |
7/5/2028 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/20/2025 |
11/20/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Dover Maglink LX Plus |
11/20/2025 |
11/20/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/26/2024 |
11/26/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/13/2023 |
11/13/2026 |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC
|
Precision Test (Piping)
|
Pass
|
11/20/2025
|
|
Tank
|
Steel Single Wall
|
Precision Test (Tank)
|
Pass
|
4/2/2025
|
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
50 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1976 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/13/2023 |
11/13/2026 |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
7/5/2023 |
7/5/2028 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/20/2025 |
11/20/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Dover Maglink LX Plus |
11/20/2025 |
11/20/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/26/2024 |
11/26/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/13/2023 |
11/13/2026 |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC
|
Precision Test (Piping)
|
Pass
|
11/20/2025
|
|
Tank
|
Steel Single Wall
|
Precision Test (Tank)
|
Pass
|
7/6/2023
|
Tank Number 3
| Capacity: |
6000 |
|
Petroleum Use: |
None |
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
50 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1976 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/13/2023 |
11/13/2026 |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
7/5/2023 |
7/5/2028 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/20/2025 |
11/20/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Dover Maglink LX Plus |
11/20/2025 |
11/20/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
4/11/2025 |
4/11/2028 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/13/2023 |
11/13/2026 |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC
|
Precision Test (Piping)
|
Pass
|
11/20/2025
|
|
Tank
|
Steel Single Wall
|
Precision Test (Tank)
|
Pass
|
7/6/2023
|
Tank Number 4
| Capacity: |
6000 |
|
Petroleum Use: |
None |
| Product: |
Racing Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
50 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1976 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
1/1/1976 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
11/13/2023 |
11/13/2026 |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Lining Materials Internal |
7/5/2023 |
7/5/2028 |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
11/20/2025 |
11/20/2026 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Dover Maglink LX Plus |
11/20/2025 |
11/20/2026 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
11/26/2024 |
11/26/2027 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
Not applicable |
Not applicable |
Leak Detect - Piping
|
Piping Sump Sensors Not Regulated Not Required |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
11/13/2023 |
11/13/2026 |
|
Tank
|
Steel Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech P175SC
|
Precision Test (Piping)
|
Pass
|
11/20/2025
|
|
Tank
|
Steel Single Wall
|
Precision Test (Tank)
|
Pass
|
7/6/2023
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found