Notice of Violatlions (Current)
NOV Number:
E0020260982
(Pending)
Issue Date:
4/14/2026
Expiration Date:
6/13/2026
View NOV Form
| Tanks |
Violations |
| 7, 8 |
Dispensers - hoses cracked, split or worn and require replacement |
| 7, 8, 9 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 7, 8 |
Water in containment without required sensors – install cathodic protection on all exposed steel piping or make containment watertight. By 10/13/28, all containments must be watertight and any CP installed in containments must be removed. - 3/4 UDC. If repairing, documentation needs to be provided from a contractor |