Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2011201
Status: Active
Facility Name: Mobil FSZM Corporation
Address: 6000 Oakton Street Morton Grove, IL 60053
County: Cook
Property Parcel: 10-20-302-037-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001088
Green Tag Issue Date: 3/13/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Oaktin Real Estate Company, Inc.
Owner Address: 6000 Oakton Street Morton Grove, IL 60053
Owner Status: Current Owner
Purchase Date: 8/28/2023
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 9/18/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 3/13/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041598 Oaktin Real Estate Company, Inc. Current Owner 8/28/2023
U0039791 Chicago Title Land Trust Co. Under Trust #52119T Former Owner 12/31/2012
U0009322 Nick & Ernie's, Inc. Former Owner 1/1/1982

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252787 (Pending)    Issue Date: 10/21/2025    Expiration Date: 12/20/2025    View NOV Form

Tanks Violations
4 Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensor(s) has/have been raised rendering it/them ineffective. Repair/replace sensor(s) into proper location so that it can function as designed.
4 Line leak detection equipment in alarm or failed test, must repair or replace. - Line leak detection equipment in alarm on ATG; Repair/replace as necessary to clear alarm. L3: North Diesel Sub Pit Fuel Alarm
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom. 2024 THROUGH OCTOBER 2025, NOT DATED.
1, 3, 4 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt, indicator lights functionality, and hour meter readings; system status, name of employee who recorded information. NO LOG FOR 2025.
4 Open electrical conduit or junction boxes. - DIESEL ATG PROBE HAS CAP OFF WHICH MAY BE ALLOWING WATER TO GET IN AND COULD BE CAUSING HIGH WATER ALARM.
1, 3, 4 Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “NORMAL” from ATG.
1, 3, 4 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth.
1, 3, 4 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 3 Tank monitor does not appear to function properly and requires maintenance. - Indicator lights on panel of Veeder-Root ATG are not functional. Replace as necessary to provide proper operation. ALL 3 Lights are non-functional.
4 Tank monitor does not appear to function properly and requires maintenance. - ATG in alarm; repair/replace as necessary to secure alarm. T3; High Water Warning. Tank has 59 gallons of water, REMOVE WATER.
4 Tank monitor does not appear to function properly and requires maintenance. - Indicator lights on panel of Veeder-Root ATG are not functional. Replace as necessary to provide proper operation. ALL 3 Lights are non-functional.
1, 3, 4 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump(s) contain(s) liquid, creating alarm on ATG. Remove liquid and repair containment to prevent further liquid ingress. Repair/replace sensor(s) as necessary to clear alarm.

NOV Number: E0020252788 (Pending)    Issue Date: 10/21/2025    Expiration Date: 12/20/2025    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.
Facility Fire Extinguishers - 2 4A:60BC extinguishers not provided - Provide min of 2 fire extinguishers (4A:60 BC rated), installed to provide access to both employees and customers.
Facility Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
99-2123 9/13/1999 Removal Log 02353-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
99-2123 Eligible 6/13/2008 7/17/2008 $10,000
20200430 Eligible 7/13/2020 7/13/2020 $5,000 Letter
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 6000 Gasoline - Premium Currently in use Federal $0.00
2 6000 Diesel Fuel Abandoned in place Federal $0.00 04/14/2020 - ABN
3 8000 Gasoline - Regular Currently in use Federal $0.00
4 8000 Diesel Fuel Currently in use Federal $0.00
5 1000 Heating Oil Removed State $0.00 09/13/1999 - REM
6 560 Used Oil Removed State $0.00 09/13/1999 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found