Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2011002
Status: Active
Facility Name: ISTHA M06 Maintenance Garage
Address: Route 20 & I-90 Northwest Tollway, Mile Post 36.5 Hampshire, IL 60140
County: Kane
Property Parcel:
Facility Type: State
Owner Type: State
Green Tag Decal: AA03813
Green Tag Issue Date: 5/7/2025
Green Tag Expiration Date: 12/31/2027

Owner Details

Owner Name: Illinois State Toll Highway Authority
Owner Address: 2700 Ogden Avenue Downers Grove, IL 60515
Owner Status: Current Owner
Purchase Date: 1/1/1973
Type of Financial Responsibility: Self-Insurance
Financial Responsibility Reporting Due Date: 3/31/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Fleet 5/7/2025 12/31/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0007425 Illinois State Toll Highway Authority Current Owner 1/1/1973

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violatlions (Current)

NOV Number: E0020252121 (Pending)    Issue Date: 8/18/2025    Expiration Date: 10/17/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation.
9 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
9 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
10 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
10 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
11 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (interstitial sensors/ATG) not completed. Testing shall be completed and submitted to OSFM.
11 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (leak detectors and/or interstitial sensors) not completed. Testing shall be performed.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
9, 10, 11 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/11/2018
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 37 Abandoned Date:
Install Date: 1/1/1981 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 1/1/1981

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/14/2017 9/14/2018
Leak Detect - Piping Sump Sensor 9/14/2017 9/14/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Overfill Alarm
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/17/1992
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 11 Abandoned Date:
Install Date: 1/1/1981 Red Tag Issue Date:
Last Used Date: 6/17/1992 Fee Due: $0.00
Product Date: 1/1/1981

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 300 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 3/9/1992
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 34 Abandoned Date:
Install Date: 1/1/1958 Red Tag Issue Date:
Last Used Date: 3/9/1992 Fee Due: $0.00
Product Date: 1/1/1958

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/18/1998
OSFM First Notify Date: 5/5/1986 Abandoned Material: Water
Current Age: 40 Abandoned Date: 1/1/1981
Install Date: 1/1/1958 Red Tag Issue Date:
Last Used Date: 1/1/1981 Fee Due: $0.00
Product Date: 1/1/1958

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 6/18/1998
OSFM First Notify Date: 5/5/1986 Abandoned Material: Water
Current Age: 40 Abandoned Date: 1/1/1981
Install Date: 1/1/1958 Red Tag Issue Date:
Last Used Date: 1/1/1981 Fee Due: $0.00
Product Date: 1/1/1958

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 10000 Petroleum Use: Consumptive Use on Premises for Heating
Product: Heating Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: State Removed Date: 4/20/1992
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 4/20/1992 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 300 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/20/1992
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 4/20/1992 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 8

Capacity: 10000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 4/11/2018
OSFM First Notify Date: 4/13/1993 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: 6/15/1992 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 6/16/1992

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 9/14/2017 9/14/2018
Leak Detect - Piping Sump Sensor 9/14/2017 9/14/2018
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Overfill Alarm
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 9

Capacity: 12000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/28/2018 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 4/20/2018 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/20/2018

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/9/2025 7/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 7/9/2025 7/9/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 7/9/2025 7/9/2026
Overfill Prev Device Overfill Alarm 7/19/2024 7/19/2027
Overfill Prev Device Overfill Drop Tube Valve 7/19/2024 7/19/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/19/2024 7/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2025 7/9/2026
Piping Single Wall Transition Sump 7/19/2024 7/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2025 7/9/2026
Piping Single Wall Transition Sump 7/19/2024 7/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2025 7/9/2026
Spill Contain Device Single Wall Spill Bucket 7/19/2024 7/19/2027
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 10

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/28/2018 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 4/20/2018 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/20/2018

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/9/2025 7/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 7/9/2025 7/9/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 7/9/2025 7/9/2026
Overfill Prev Device Overfill Alarm 7/19/2024 7/19/2027
Overfill Prev Device Overfill Drop Tube Valve 7/19/2024 7/19/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/19/2024 7/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2025 7/9/2026
Spill Contain Device Single Wall Spill Bucket 7/19/2024 7/19/2027
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 11

Capacity: 10000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 11/28/2018 Abandoned Material:
Current Age: 6 Abandoned Date:
Install Date: 4/20/2018 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 9/20/2018

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 7/9/2025 7/9/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 Plus with CSLD 7/9/2025 7/9/2026
Leak Detect - Tank Hydrostatic Reservoir Interstitial Monitoring Sensors 7/9/2025 7/9/2026
Overfill Prev Device Overfill Alarm 7/19/2024 7/19/2027
Overfill Prev Device Overfill Drop Tube Valve 9/5/2024 9/5/2027
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/19/2024 7/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2025 7/9/2026
Spill Contain Device Double Wall Spill Bucket 9/5/2024 9/5/2027
Tank Fiberglass Brine Filled Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Tank Fiberglass Brine Filled Double Wall XERXES Precision Test (Tank) Pass 9/5/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/19/2024 7/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2025 7/9/2026



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump 7/19/2024 7/19/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/9/2025 7/9/2026

MFD Motorfuel Dispensing Forms

No Forms Found