Notice of Violations (Current)
NOV Number:
E0020251044
(Pending)
Issue Date:
4/16/2025
Expiration Date:
6/15/2025
View NOV Form
Tanks |
Violation |
Facility |
Code complying instruction/warning signs are not properly mounted at each dispenser island - Self-service instructional signs at dispensers are missing or do not meet minimum requirements. Install appropriate signage. |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |
Facility |
Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly. |
NOV Number:
E0020251046
(Pending)
Issue Date:
4/16/2025
Expiration Date:
6/15/2025
View NOV Form
Tanks |
Violation |
4, 5, 6 |
Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensors have been raised rendering them ineffective at the regular STP & Dispenser 11/12. Repair/replace sensors into proper location so they can function as designed. |
Facility |
Missing copies of current testing certificates for operator training - Copies of all current Class C testing certificates shall be maintained on file on site.
Go to www.sfm.illinois.gov (UST Operator Training) to find current information regarding Operator
Training requirements, including all relevant forms. |
Facility |
Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current. |
4, 5, 6 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
4, 5, 6 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator lights (YELLOW & GREEN) on panel of Veeder-Root ATG are not functional. Replace as necessary to provide proper operation. |