Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2010842
Status: Active
Facility Name: Fahd Amoco, Inc.
Address: 1 Waukegan
Deerfield, IL 60015
County: Lake
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y001249
Green Tag Issue Date: 5/30/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Mohammed Amiani
Owner Address: 1 Waukegan Rd
Deerfield, IL 60015
Owner Status: Current Owner
Purchase Date: 10/19/2006
Type of Financial Responsibility: Certificate of Deposit
Financial Responsibility Reporting Due Date: 9/13/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/30/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0033884 Amiani, Mohammed Current Owner 10/19/2006
U0023834 BP Amoco Former Owner 4/14/1995
U0027493 Amoco Oil Company Former Owner
U0000552 BP Products North America, Inc. Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00540-2025CAT Cathodic Protection Approved / Issued 5/6/2025 5/6/2025 11/6/2025 Documents

Notice of Violations (Current)

NOV Number: E0020251057 (Pending)    Issue Date: 4/17/2025    Expiration Date: 6/16/2025    View NOV Form

Tanks Violation
2, 3, 4, 5 Inventory control is no longer acceptable, another form of leak detection is required. - Must show 24 months of passing results from Titan or install printer and provide passing reciepts monthly.
Facility Miscellaneous - Emergency stop shall be readily accessible and conspicuously marked by a sign on all-weather materials stating "EMERGENCY STOP" in 2 inch red capital letters. (Per 41 Ill Admin code 175.210(d)(3))
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom.
2, 3, 4, 5 Monthly line interstitial sensor records not available. - Maintain one PASS report per LINE, per month, from ATG. (Titan)
2, 3, 4, 5 Required monthly tank leak test records not available. - Maintain one PASS report per TANK, per month, from tank monitor.
2, 3, 4, 5 Tank monitor does not appear to function properly and requires maintenance. - Indicator light on tank monitor is not functional. Warning light and green light is out.
5 Tank precision test required. - ATG shows 152 gallons of water in tank. Investigate cause of water ingress.
4 Water in containment without required interstitial sensors - install cathodic protection on all exposed steel. - Fuel in STP containment sump.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

No Applications Found

Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 500 Used Oil Removed Exempt 01/01/1985 - REM
2 8000 Gasoline - Regular Currently in use Federal $0.00
3 8000 Gasoline - Regular Currently in use Federal $0.00
4 8000 Gasoline - Premium Currently in use Federal $0.00
5 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found