Facility Details

Facility Number: 2010838
Status: Active
Facility Name: Crystal Lake Amoco
Address: 339 W. Virginia Street
Crystal Lake, IL 60014
County: McHenry
Property Parcel: 19-05-308-026
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003251
Green Tag Issue Date: 8/2/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: Crystal Lake Real Estate, Inc.
Owner Address: 502 Pratt Ave., North
Schaumburg, IL 60193
Owner Status: Current Owner
Purchase Date: 11/27/2018
Type of Financial Responsibility: Designated Savings Account
Financial Responsibility Reporting Due Date: 5/29/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/2/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039664 Crystal Lake Real Estate, Inc. Current Owner 11/27/2018
U0031897 Ohmshiva Corporation Former Owner 12/29/2003
U0000552 BP Products North America, Inc. Former Owner 12/29/2003
U0023834 BP Amoco Former Owner 4/13/1995
U0027493 Amoco Oil Company Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250685 (Pending)    Issue Date: 3/17/2025    Expiration Date: 5/16/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available.
1, 2, 3 Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Section 175.410 Submersible, Under-dispenser, Transition and Other Containment Sumps a) All containment sumps must consist of a factory manufactured containment that is liquid-tight on its sides, bottom and at any penetrations and is compatible with the substance conveyed by the piping. Such containment shall also have a factory manufactured protective cover and supporting components that are properly maintained. If the protective cover or its supporting components are cracked, deteriorated or missing, the cover and supporting components that are defective shall be replaced. SPECIFICALLY ALL 3 ATG LIDS ARE BROKEN AND COVERED BY GARBAGE CANS OR BROKEN. THE REG STP LID HAS NO HANDLE.
Facility Missing copies of 30 day Walkthrough Inspection Report. - 30-day Walkthrough Inspection shall be completed, and 2 years of documentation maintained on site. 30-Day Walkthrough Inspection form available at www.sfm.illinois.gov. The form must be filled out by an A/B Operator, you must, initial each box that applies, date the form each month to ensure it is being done every 30 days, and the A/B operator must print and sign their name at the bottom. If more than one A/B operator fills out the form, then each must print and sign name at the bottom. Not filling in the Impressed current system portion, Not printing ATG monthly.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site.
Facility Missing copy of written UST facility operation & maintenance plan - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site.
Facility Missing list of designated Class A/B & C Operators - A comprehensive list of Class A / B / C Operator(s) shall be maintained on site and must be current. LIST IS NOT CURRENT OR MAINTAINED.
1, 2, 3 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt, indicator lights functionality, and hour meter readings; system status, name of employee who recorded information. Log is not being read correctly, hours are wrong, and the rectifier was turned off upon arrival.
1, 2, 3 Precision tank test required. - Precision tank test is required on tank(s) if you cannot provide 24 months’ worth of tank “PASS” from ATG.
1, 2, 3 Required monthly tank leak test records not available. - Maintain one PASSing report per TANK, per month, from ATG. Must maintain 24 months’ worth. After Precision tank test you must maintain your leak detection and provide monthly tank "PASS" from the ATG.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
1, 2, 3 Tank monitor does not appear to function properly and requires maintenance. - Indicator YELLOW WARNING light on panel of Veeder-Root ATG is not functional. Replace as necessary to provide proper operation.

NOV Number: E0020250688 (Pending)    Issue Date: 3/17/2025    Expiration Date: 5/16/2025    View NOV Form

Tanks Violation
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-1685 Eligible 2/18/2004 3/1/2004 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 12000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found