Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0041011 |
802 West Palatine, LLC |
Current Owner |
9/15/2023 |
| U0038573 |
Palatine Land, LLC |
Former Owner |
3/12/2016 |
| U0032420 |
Quentin & Palatine Citgo, Inc. |
Former Owner |
9/30/2004 |
| U0027042 |
TGS New Enterprises Limited, LLC |
Former Owner |
11/11/1998 |
| U0025970 |
PDV Midwest Refining Llc |
Former Owner |
5/1/1997 |
| U0015441 |
The Uno Ven Company |
Former Owner |
4/5/1993 |
| U0029182 |
Palatine Citgo |
Former Owner |
|
Notice of Violations (Current)
NOV Number:
E0020261759
(Pending)
Issue Date:
7/9/2026
Expiration Date:
9/7/2026
View NOV Form
| Tanks |
Violations |
| 2 |
Containment support components are cracked, deteriorated or missing. The cover and supporting components that are defective shall be replaced with factory manufactured components. - Replace steel ring and STPlid. Rusted and not seating properly. |
| 2, 3, 4 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - Remove Liquid |
| 2, 3, 4 |
Tank monitor does not appear to function properly and requires maintenance. - Green indicator light is out and needs to be replaced. |
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 92-0357 |
Returned |
10/18/2004
|
10/27/2004
|
$Not Selected
|
|
| 92-0357 |
Eligible |
4/22/2013
|
6/7/2013
|
$10,000
|
|
Tank Number 1
| Capacity: |
1000 |
|
Petroleum Use: |
|
| Product: |
Heating Oil |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
2/8/2002 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
34 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
1/1/1999 |
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
44 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1982 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
1/22/2026 |
1/22/2029 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
1/22/2026 |
1/22/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 |
1/22/2026 |
1/22/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/5/2024 |
2/5/2027 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/31/2024 |
1/31/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
1/22/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
2/2/2024
|
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
58 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Sacrificial Anode Flex Connector |
1/22/2026 |
1/22/2029 |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
1/22/2026 |
1/22/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 |
1/22/2026 |
1/22/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
2/13/2024 |
2/13/2027 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Not Installed STP/Tanktop Sump |
Not applicable |
Not applicable |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/31/2024 |
1/31/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
1/22/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
1/31/2024
|
Tank Number 4
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Diesel Fuel |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
58 |
|
Abandoned Date: |
|
| Install Date: |
1/1/1968 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
|
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Pressurized Line Leak Detection |
1/22/2026 |
1/22/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 300 |
1/22/2026 |
1/22/2027 |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/31/2024 |
1/31/2027 |
|
Piping
|
Flex Connector Steel |
Not applicable |
Not applicable |
|
Piping
|
Fiberglass Single Wall Piping |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
3/19/2024 |
3/19/2027 |
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
3/19/2024 |
3/19/2027 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
1/31/2024 |
1/31/2027 |
|
Tank
|
Fiberglass Single Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Fiberglass Single Wall Piping
|
Precision Test (Piping)
|
Pass
|
4/7/2026
|
|
Tank
|
Fiberglass Single Wall
|
Precision Test (Tank)
|
Pass
|
4/7/2026
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
Dispenser Information
Name\ID 1/2
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 3/4
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 5/6
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Not Installed UDC Sump |
Not applicable
|
Not applicable
|
Name\ID 7/8
| Status: |
Active |
|
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Dispenser
|
Single Wall UDC Sump |
3/19/2024
|
3/19/2027
|
Leak Detect - Piping
|
Sump Sensor with positive shutdown |
1/22/2026
|
1/22/2027
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found