Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually, and must be maintained until the tanks are removed or properly abandoned in place by a licensed UST decommissioning contractor. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
| 6 |
Line interstitial sensors have been raised and rendered inoperational. - Interstitial sensors has been raised rendering it ineffective. Repair/replace sensors into proper location so that it can function as designed. |
| 6, 7, 8 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
| 6, 7, 8 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator lights on panel of Veeder-Root ATG are not functional. Replace as necessary to provide proper operation. ALL 3 LIGHTS ARE OUT. |
| 6 |
Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - STP sump contains liquid, it would be creating alarm on ATG, but sensor has been raised out of the liquid. Remove liquid and repair containment to prevent further liquid ingress. Repair/replace sensor to proper position. |