Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete. |
4, 5 |
Line interstitial sensor functional test not accomplished (Required annually). |
4, 5 |
Mechanical line leak detector requires annual functional test. |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - Shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/30-day-walkthrough-inspection-report.pdf (No documentation since March of 2025) |
4, 5 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
Facility |
Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form. |
4, 5 |
Tank interstitial sensor functional test not accomplished (Required annually). |
4, 5 |
Triennial spill prevention equipment testing not completed. |
4, 5 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). |