Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2010054
Status: Active
Facility Name: Citgo
Address: 750 Glenwood Dryer Road Glenwood, IL 60425
County: Cook
Property Parcel: 32-11-108-026-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001354
Green Tag Issue Date: 12/12/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: Jagtar Singh
Owner Address: 750 Glenwood Dryer Road Glenwood, IL 60425
Owner Status: Current Owner
Purchase Date: 7/1/1998
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 12/10/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/12/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0028747 Singh, Jagtar Current Owner 7/1/1998
U0003073 Clark Retail Enterprises, Inc. Former Owner 11/22/1988

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00969-2025UPG Upgrade Approved / Issued 7/25/2025 7/28/2025 1/28/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020252011 (Pending)    Issue Date: 8/8/2025    Expiration Date: 10/7/2025    View NOV Form

Tanks Violations
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
4, 5 Line interstitial sensor functional test not accomplished (Required annually).
4, 5 Mechanical line leak detector requires annual functional test.
Facility Missing copies of 30 day Walkthrough Inspection Report. - Shall be completed, and documentation maintained on site. 30-Day Walkthrough Inspection form available at https://sfm.illinois.gov/content/dam/soi/en/web/sfm/sfmdocuments/documents/30-day-walkthrough-inspection-report.pdf (No documentation since March of 2025)
4, 5 Overfill prevention equipment inspection(s) not completed (Required every 3 years).
Facility Submit Notification Form For Ownership Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Select “New Owner” as the type of notification form.
4, 5 Tank interstitial sensor functional test not accomplished (Required annually).
4, 5 Triennial spill prevention equipment testing not completed.
4, 5 Triennial testing for qualifying piping containment sump not completed (Required every 3 years).

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
99-1943 8/17/1999 Removal Log 02297-1999REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-0268 Eligible 5/16/1995 6/1/1995 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/17/1999
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 2/28/1995 Fee Due: $0.00
Product Date: 1/1/1971

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/17/1999
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 11/21/1996 Fee Due: $0.00
Product Date: 1/1/1971

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 8/17/1999
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: 1/1/1971 Red Tag Issue Date:
Last Used Date: 11/21/1996 Fee Due: $0.00
Product Date: 1/1/1971

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 8/19/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 with CSLD 10/10/2024 10/10/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Overfill Prev Device Overfill Drop Tube Valve 3/14/2022 3/14/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 3/14/2022 3/14/2025
Leak Detect - Piping Sump Sensor 3/4/2024 3/4/2025
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Single Wall Spill Bucket 3/14/2022 3/14/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 3/4/2024
Tank Fiberglass Double Wall Precision Test (Tank) Pass 10/21/2020



Tank Number 5

Capacity: 8000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 8/31/1999 Abandoned Material:
Current Age: 26 Abandoned Date:
Install Date: 8/19/1999 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 3/4/2024 3/4/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 300 with CSLD 10/10/2024 10/10/2025
Leak Detect - Tank Non-Discriminating Interstitial Monitoring Sensors 3/4/2024 3/4/2025
Overfill Prev Device Overfill Drop Tube Valve 3/14/2022 3/14/2025
Piping Fiberglass Double Wall N/A N/A
Piping Single Wall STP/Tanktop Sump 3/14/2022 3/14/2025
Leak Detect - Piping Sump Sensor 3/4/2024 3/4/2025
Leak Detect - Piping Sump Sensor with positive shutdown 3/4/2024 3/4/2025
Spill Contain Device Single Wall Spill Bucket 3/14/2022 3/14/2025
Tank Fiberglass Double Wall XERXES N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 3/4/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

Facility Number Name City Received Date Letter
2010054 Citgo Glenwood 07/25/2025 Letter Form