Notice of Violatlions (Current)
NOV Number:
E0020252830
(Pending)
Issue Date:
10/22/2025
Expiration Date:
12/21/2025
View NOV Form
| Tanks |
Violations |
| 3, 4 |
Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Last test was 2/17/2022. |
| 3, 4 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Last test was 2/17/2022 |
| 3, 4 |
Triennial spill prevention equipment testing not completed. - Last test was 2/17/2022. |
NOV Number:
E0020252836
(Pending)
Issue Date:
10/24/2025
Expiration Date:
12/23/2025
View NOV Form
| Tanks |
Violations |
| Facility |
Submit Notification Form For Ownership Change - Per 41 Ill. Adm. Code 176.440 (g), a change of ownership information must be reported on an electronic Notification for Underground Storage Tank form, within 30 days of the change. According to the Will County Property Portal, it states that N & P Dhillon LLC is the owner. The Notification Form is available at: https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. |