Notice of Violations (Current)
NOV Number:
E0020251264
(Pending)
Issue Date:
5/14/2025
Expiration Date:
7/13/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020251265
(Pending)
Issue Date:
5/14/2025
Expiration Date:
7/13/2025
View NOV Form
Tanks |
Violation |
Facility |
Facility Operation and Maintenance Plan not updated to new requirements. - Facility Operations and Maintenance Plan does not meet requirements of new rules. Go to https://sfm.illinois.gov to download and complete O & M template and maintain completed form on site. (Update with new template.) |
4, 5 |
Piping interstitial must be open in all sumps - Product piping test boots shall be pulled back after testing to allow the interstice to be open to the sump sensors. Reference 175.420 b) (Or Shrader valves need to be removed) (Premium STP, Disp. 1/2 and 3/4) |
NOV Number:
E0020251267
(Pending)
Issue Date:
5/14/2025
Expiration Date:
7/13/2025
View NOV Form
Tanks |
Violation |
Facility |
Financial responsibility must be reported yearly - Financial Responsibility form can be found at https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |