Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2009902
Status: Closed
Facility Name: B & K Mart, Inc.
Address: 830 East Lake Avenue
Woodstock, IL 60098
County: McHenry
Property Parcel:
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: P001417
Green Tag Issue Date: 6/12/2014
Green Tag Expiration Date: 12/31/2016

Owner Details

Owner Name: Star Gas Mart, Inc.
Owner Address: 830 East Lake Ave.
Woodstock, IL 60098
Owner Status: Current Owner
Purchase Date: 1/1/2014
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/4/2015

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/12/2014 12/31/2016

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037182 Star Gas Mart, Inc. Current Owner 1/1/2014
U0036752 Saheli 830 Corp. Former Owner 12/21/2012
U0035173 SAS Fuels, Inc. Former Owner 11/19/2005
U0003073 Clark Retail Enterprises, Inc. Former Owner 11/22/1988
U0029789 Clark Retail Enterprises, Inc. Former Owner
U0028787 Clark Retail Enterprises, Inc., Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Deficiencies (Current)

NOV Number: E0020150918 (Referred to Legal)    Issue Date: 4/9/2015    Expiration Date: 6/8/2015    View NOV Form

Tanks Deficiency
1, 2, 3 Annual tank impressed current system appears not to be operational. - All Power to Rectifier has been turned off.
1, 2, 3 Failed to Empty the Tank to 1" or Less
Facility Financial responsibility must be reported yearly - Financial Responsibility shall be declared annually; declaration form left on site. Complete form and mail to highlighted address at top of form.
1, 2, 3 Flex connector sacrificial anode system not tested (required every 3 years) - Test anodes and replace as needed - Three-year third party testing required on sacrificial anode/cathodic protection system. Perform annual testing and maintain passing documentation on site for review by OSFM Inspector.
1, 2, 3 Monthly impressed current system log not available or maintained. - A log showing the rectifier gauge readings from Impressed Current rectifier shall be maintained monthly on site for review by OSFM Inspector. Log shall show date; amp, volt and hour meter readings; who recorded information.
Facility Submit Notification Form For Ownership Change - Submit OSFM Notification Form showing change in facility ownership. Notification form is available at www.sfm.illinois.gov
1, 2, 3 Submit Notification Form For Tank Status Change - Submit OSFM Notification Form placing all tanks in Temporarily Out of Use status. Notification form is available at www.sfm.illinois.gov

NOV Number: E0020160119 (Formal)    Issue Date: 1/20/2016    Expiration Date: 3/20/2016    View NOV Form

Tanks Deficiency
1, 2, 3 Remove tank(s) - Corrosion Protection not Maintained
1, 2, 3 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year

NOV Number: E0020170928 (Formal)    Issue Date: 3/27/2017    Expiration Date: 5/26/2017    View NOV Form

Tanks Deficiency
1, 2, 3 Remove tank(s) - Corrosion Protection not Maintained
1, 2, 3 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year

NOV Number: E0020170929 (Formal)    Issue Date: 3/27/2017    Expiration Date: 5/26/2017    View NOV Form

Tanks Deficiency
1, 2, 3 Remove tank(s) - Corrosion Protection not Maintained
1, 2, 3 Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
19-1221 11/26/2019 Removal Log 02101-2019REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
95-1102 Eligible 8/29/1995 10/2/1995 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/26/2019
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 49 Abandoned Date:
Install Date: 10/1/1970 Red Tag Issue Date:
Last Used Date: 1/15/2015 Fee Due: $0.00
Product Date: 10/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 3/1/2012 3/1/2015
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 6/12/2014 6/12/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/12/2014 6/12/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Ball Float Vent Valve OPW 53
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/26/2019
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 49 Abandoned Date:
Install Date: 10/1/1970 Red Tag Issue Date:
Last Used Date: 1/15/2015 Fee Due: $0.00
Product Date: 10/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 3/1/2012 3/1/2015
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 6/12/2014 6/12/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/12/2014 6/12/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Ball Float Vent Valve OPW 53
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 7500 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/26/2019
OSFM First Notify Date: 5/2/1986 Abandoned Material:
Current Age: 49 Abandoned Date:
Install Date: 10/1/1970 Red Tag Issue Date:
Last Used Date: 1/15/2015 Fee Due: $0.00
Product Date: 10/1/1970

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 3/1/2012 3/1/2015
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Impressed Current Cathodic Protection 6/12/2014 6/12/2015
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 6/12/2014 6/12/2015
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD
Overfill Prev Device Ball Float Vent Valve OPW 53
Piping Fiberglass Single Wall Piping N/A N/A
Spill Contain Device Single Wall Spill Bucket
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



MFD Motorfuel Dispensing Forms

No Forms Found