Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2009165
Status: Active
Facility Name: Windy Station, Inc.
Address: 18259 S. Crawford Ave.
Country Club Hills, IL 60478
County: Cook
Property Parcel: 28-35-302-043-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002024
Green Tag Issue Date: 6/12/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 18259 Crawford Property, LLC
Owner Address: 8550 S. Harlem Avenue
Suite G
Bridgeview, IL 60455
Owner Status: Current Owner
Purchase Date: 3/21/2023
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/26/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 8/16/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040977 18259 Crawford Property, LLC Current Owner 3/21/2023
U0040301 Majid RE, LLC Former Owner 8/7/2020
U0039542 Ketankumar K Soni Former Owner 9/6/2018
U0031904 Reddy, Ramachandra Former Owner 3/5/2004
U0008842 Lake Shore Petroleum Corporation Former Owner 6/7/1994
U0010471 Exxon Mobil Oil Corporation Former Owner 12/31/1967

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020251101 (Pending)    Issue Date: 4/23/2025    Expiration Date: 6/22/2025    View NOV Form

Tanks Violation
3, 4 Verify and test piping sump sensor for positive shutdown - Still able to pump while sensor is in alarm.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
2024-0531 7/19/2024 Abandonment Log 00799-2024ABN
N/A 10/4/2023 Removal Log 00982-2023REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
87-0553 Eligible 4/12/1994 4/28/1994 $50,000
90-0279 Returned 4/30/2001 5/17/2001 $Not Selected
90-0279 Eligible 5/23/2001 6/14/2001 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 6000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 42 Abandoned Date:
Install Date: 11/24/1982 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/8/2024 7/8/2025
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 7/8/2024 7/8/2025
Overfill Prev Device Overfill Drop Tube Valve 6/15/2023 6/15/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/8/2024 7/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/8/2024 7/8/2025
Spill Contain Device Single Wall Spill Bucket 5/8/2023 5/8/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 7/8/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 8/25/2023



Tank Number 2

Capacity: 6000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Abandoned in place CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material: Inert material mixed with portland cement
Current Age: 41 Abandoned Date: 7/19/2024
Install Date: 8/16/1983 Red Tag Issue Date:
Last Used Date: 5/1/2023 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 7/23/2020 5/9/2023
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 9/7/2021 9/7/2022
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 4/19/2023 4/19/2024
Overfill Prev Device Overfill Drop Tube Valve 7/25/2019 7/25/2022
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall Transition Sump 5/8/2023 5/8/2026
Leak Detect - Piping Sump Sensor 4/19/2023 4/19/2024
Spill Contain Device Single Wall Spill Bucket 5/8/2023 5/8/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 9/7/2021
Tank Fiberglass Single Wall Precision Test (Tank) Fail 1/19/2023



Tank Number 3

Capacity: 10000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 8/16/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/8/2024 7/8/2025
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 7/8/2024 7/8/2025
Overfill Prev Device Overfill Drop Tube Valve 8/24/2023 8/24/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/8/2024 7/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/8/2024 7/8/2025
Spill Contain Device Single Wall Spill Bucket 5/8/2023 5/8/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 7/8/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 8/25/2023



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 8/16/1983 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 7/8/2024 7/8/2025
Leak Detect - Tank Automatic Tank Gauging Gilbarco EMC with CSLD 7/8/2024 7/8/2025
Overfill Prev Device Overfill Drop Tube Valve 8/24/2023 8/24/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump 7/8/2024 7/8/2027
Leak Detect - Piping Sump Sensor with positive shutdown 7/8/2024 7/8/2025
Spill Contain Device Double Wall Spill Bucket 8/24/2023 8/24/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 7/8/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 7/8/2024



Tank Number 5

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/13/1989
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 25 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: 11/11/1989 Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 6

Capacity: 1000 Petroleum Use: None
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 2/22/2002
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 12 Abandoned Date:
Install Date: 1/1/1990 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 7

Capacity: 550 Petroleum Use: None
Product: Waste Oil CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Non-Regulated Removed Date:
OSFM First Notify Date: 8/30/2023 Abandoned Material:
Current Age: Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found