| 5, 6, 7 |
Failed to Empty the Tank to 1" or Less - Per 175.810(a)(1), when placing tanks out of service, the tank and lines must be emptied immediately. The UST is considered empty when all materials have been removed to one inch or less. It appears that there is still product in all three tanks (18, 19 & 10 inches). Product must be removed immediately! |
| Facility |
Financial responsibility must be reported yearly - Per 176.220, tank owners/operators must submit an electronic Financial Responsibility (FR) Report form on an annual basis. Financial Responsibility must be maintained until the tanks are removed or properly abandoned in place by a licensed UST decommissiong contractor. The last FR report form expired on 7/12/22. The form can be found at: https://webapps.sfm.illinois.gov/USTPortal/Forms/FinancialResponsibility. |
| 5, 6, 7 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - All three single walled tanks were taken out of service on 2/1/22, and are 39 years old. Per 175.810(e) tanks must be removed as they are now condemned. Here is a link to the licensed UST Decommissioning contractors, that can perform UST tank removals: https://webapps.sfm.illinois.gov/ustsearch/ContractorSearch.aspx |