Owner Summary
Click for Facility/Tank Ownership history
| Owner Number |
Owner Name |
Owner Status |
Purchase Date |
| U0041730 |
1700 Algonquin Real Estate Inc. |
Current Owner |
12/15/2025 |
| U0002560 |
Casey's Retail Company |
Former Owner |
5/14/2021 |
| U0036013 |
Buchanan Energy (N), LLC |
Former Owner |
12/9/2010 |
| U0010471 |
ExxonMobil Oil Corporation |
Former Owner |
|
Notice of Violations (Current)
No Notice of Violations Found
IEMA Numbers Associated with the Facility
No IEMA Numbers Found
LUST
Fund Eligibility and Deductibility Determinations
| IEMA Number |
Status |
OSFM Received Date |
OSFM Response Date |
Deductible |
Letter |
| 95-2062 |
Returned |
11/5/1999
|
11/19/1999
|
$10,000
|
|
| 20230399 |
Eligible |
10/15/2024
|
10/16/2024
|
$5,000
|
Letter
|
| 20230399 |
Eligible |
10/15/2024
|
10/16/2024
|
$5,000
|
Letter
|
Tank Number 1
| Capacity: |
8000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
9/21/1995 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
16 |
|
Abandoned Date: |
|
| Install Date: |
10/1/1978 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
9/20/1995 |
|
Fee Due: |
$0.00 |
| Product Date: |
10/1/1978 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 2
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
9/21/1995 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
16 |
|
Abandoned Date: |
|
| Install Date: |
10/1/1978 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
9/20/1995 |
|
Fee Due: |
$0.00 |
| Product Date: |
10/1/1978 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 3
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline |
|
CERCLA Substance: |
|
| Status: |
Removed |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
9/21/1995 |
|
OSFM
First Notify Date: |
5/5/1986 |
|
Abandoned Material: |
|
| Current Age: |
16 |
|
Abandoned Date: |
|
| Install Date: |
10/1/1978 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
9/20/1995 |
|
Fee Due: |
$0.00 |
| Product Date: |
10/1/1978 |
|
|
|
Equipment Information
No Equipment Listed
Additional Tests
No Tests Listed
Tank Number 4
| Capacity: |
15000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/17/1997 |
|
Abandoned Material: |
|
| Current Age: |
30 |
|
Abandoned Date: |
|
| Install Date: |
9/22/1995 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/7/1995 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/30/2026 |
3/30/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
3/30/2026 |
3/30/2027 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/21/2025 |
1/21/2028 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
3/30/2026 |
3/30/2029 |
Leak Detect - Piping
|
Sump Sensor |
3/30/2026 |
3/30/2029 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/30/2026 |
3/30/2029 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC
|
Precision Test (Piping)
|
Pass
|
7/13/2023
|
Tank Number 5
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Regular |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/17/1997 |
|
Abandoned Material: |
|
| Current Age: |
30 |
|
Abandoned Date: |
|
| Install Date: |
9/22/1995 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/7/1995 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Mechanical Other Non-vented check valve |
Not applicable |
Not applicable |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
3/30/2026 |
3/30/2027 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/21/2025 |
1/21/2028 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
3/30/2026 |
3/30/2029 |
Leak Detect - Piping
|
Sump Sensor |
3/30/2026 |
3/30/2029 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/30/2026 |
3/30/2029 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC
|
Precision Test (Piping)
|
Pass
|
7/13/2023
|
Tank Number 6
| Capacity: |
10000 |
|
Petroleum Use: |
|
| Product: |
Gasoline - Premium |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/17/1997 |
|
Abandoned Material: |
|
| Current Age: |
30 |
|
Abandoned Date: |
|
| Install Date: |
9/22/1995 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/7/1995 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/30/2026 |
3/30/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
3/30/2026 |
3/30/2027 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/21/2025 |
1/21/2028 |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
3/30/2026 |
3/30/2029 |
Leak Detect - Piping
|
Sump Sensor |
3/30/2026 |
3/30/2029 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/30/2026 |
3/30/2029 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC
|
Precision Test (Piping)
|
Pass
|
7/13/2023
|
|
Piping
|
Flexible Double Wall Environ Geo Flex
|
Precision Test (Piping)
|
Pass
|
9/10/2020
|
Tank Number 7
| Capacity: |
5000 |
|
Petroleum Use: |
|
| Product: |
B-11 |
|
CERCLA Substance: |
|
| Status: |
Currently in use |
|
CAS Code: |
|
| Regulated Status: |
Federal |
|
Removed Date: |
|
|
OSFM
First Notify Date: |
7/17/1997 |
|
Abandoned Material: |
|
| Current Age: |
30 |
|
Abandoned Date: |
|
| Install Date: |
9/22/1995 |
|
Red Tag Issue Date: |
|
| Last Used Date: |
|
|
Fee Due: |
$0.00 |
| Product Date: |
11/7/1995 |
|
|
|
Equipment Information
| Equipment Type |
Equipment |
Last Passing Date |
Test Expire Date |
|
Corrosion Prot - Piping
|
Flexible Non-Corrosive |
Not applicable |
Not applicable |
|
Corrosion Prot - Tank
|
Fiberglass Non-Corrosive |
Not applicable |
Not applicable |
|
Leak Detect - Piping
|
Electronic Pressurized Line Leak Detection |
3/30/2026 |
3/30/2027 |
|
Leak Detect - Tank
|
Automatic Tank Gauging Veeder Root TLS 350 with CSLD |
3/30/2026 |
3/30/2027 |
|
Overfill Prev Device
|
Ball Only Removed Ball Float Vent Valve |
Not applicable |
Not applicable |
|
Overfill Prev Device
|
Overfill Drop Tube Valve |
1/21/2025 |
1/21/2028 |
|
Piping
|
Flexible Double Wall Environ Geo Flex |
Not applicable |
Not applicable |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC |
Not applicable |
Not applicable |
|
Piping
|
Single Wall STP/Tanktop Sump |
3/30/2026 |
3/30/2029 |
Leak Detect - Piping
|
Sump Sensor |
3/30/2026 |
3/30/2029 |
|
Spill Contain Device
|
Single Wall Spill Bucket |
3/30/2026 |
3/30/2029 |
|
Tank
|
Fiberglass Double Wall |
Not applicable |
Not applicable |
Additional Tests
| Equipment Type |
Equipment |
Test Type |
Test Result |
Test Date |
|
Piping
|
Flexible Double Wall A.P.T. Poly Tech S175SC
|
Precision Test (Piping)
|
Pass
|
7/13/2023
|
Failed test = the latest test has failed.
Not applicable = a test does not apply to this equipment type or configuration.
No passing test found = a passing test is expected but was not found from the source data.
MFD
Motorfuel Dispensing Forms
No Forms Found