Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2009090
Status: Active
Facility Name: Marathon
Address: 2800 West 63rd Street
Chicago, IL 60629
County: Cook
Property Parcel: 19-13-31-039-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002197
Green Tag Issue Date: 12/18/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: AZ SPE, LLC
Owner Address: 12345 S. Keeler Ave.
Alsip, IL 60803
Owner Status: Current Owner
Purchase Date: 10/2/2016
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 2/16/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/18/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0037844 AZ SPE, LLC Current Owner 10/2/2016
U0032207 Zahdan, Ahmad Former Owner 3/11/1999
U0010471 Exxon Mobil Oil Corporation Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250196 (Pending)    Issue Date: 1/23/2025    Expiration Date: 3/24/2025    View NOV Form

Tanks Violation
5, 6, 7 Document that emergency shut-off (shear valves) are in proper working order
Facility Financial responsibility must be reported yearly
7 Line interstitial sensors have been raised and rendered inoperational.
Facility Missing copies of 30 day Walkthrough Inspection Report.
Facility Missing copies of Annual Walkthrough Inspection Report.
Facility Missing copies of current testing certificates for operator training
Facility Missing list of designated Class A/B & C Operators
5, 6, 7 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection).

NOV Number: E0020250785 (Pending)    Issue Date: 3/25/2025    Expiration Date: 5/24/2025    View NOV Form

Tanks Violation
7 Miscellaneous - Repair/replace sensor (ATG alarm sensor out)

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
88-1471 Eligible 12/14/1993 12/29/1993 $50,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/18/1988
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 11/7/1988 Fee Due: $0.00
Product Date: 11/7/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/18/1988
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 11/7/1988 Fee Due: $0.00
Product Date: 11/7/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 6000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/18/1988
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 11/7/1988 Fee Due: $0.00
Product Date: 11/7/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 11/18/1988
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 0 Abandoned Date:
Install Date: 1/1/1970 Red Tag Issue Date:
Last Used Date: 11/7/1988 Fee Due: $0.00
Product Date: 11/7/1988

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/23/2023 8/23/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/16/2024 8/16/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 8/16/2024 8/16/2025
Overfill Prev Device Ball Float Vent Valve 8/24/2023 8/24/2026
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/28/2022 12/28/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/7/2020
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/16/2024



Tank Number 6

Capacity: 10000 Petroleum Use:
Product: E85 CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Lining Materials Internal Enviroline 375 9/28/2022 9/28/2027
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/16/2024 8/16/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 8/16/2024 8/16/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 12/20/2022 12/20/2025
Piping Flexible Double Wall A.P.T. Poly Tech P150SC N/A N/A
Piping Single Wall STP/Tanktop Sump 10/10/2022 10/10/2025
Leak Detect - Piping Sump Sensor with positive shutdown 8/16/2024 8/16/2025
Spill Contain Device Single Wall Spill Bucket 12/28/2022 12/28/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/7/2020
Piping Flexible Double Wall A.P.T. Poly Tech P150SC Precision Test (Piping) Pass 8/16/2024
Tank Fiberglass Single Wall Precision Test (Tank) Pass 9/30/2022



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 7/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 8/23/2023 8/23/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 8/16/2024 8/16/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350R with CSLD 8/16/2024 8/16/2025
Overfill Prev Device Ball Only Removed Ball Float Vent Valve N/A N/A
Overfill Prev Device Overfill Drop Tube Valve 12/20/2022 12/20/2025
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 12/28/2022 12/28/2025
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Double Wall Precision Test (Piping) Pass 10/7/2020
Piping Fiberglass Double Wall Ameron Dualoy 3000/LCX Precision Test (Piping) Pass 8/16/2024



Tank Number 8

Capacity: 1000 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Does Not Exist CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 7/1/1989 Red Tag Issue Date:
Last Used Date: 7/1/2009 Fee Due: $0.00
Product Date: 7/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found