| 5, 6, 7 |
Annual electronic line leak detector test not completed. |
| Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. |
| 5, 6, 7 |
Annual leak detection certification not completed (Required annually). |
| Facility |
Missing copies of Annual Walkthrough Inspection Report. |
| 7 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). |
| 7 |
Precision line test required. - ATG showed .10 test results for tanks 5 & 6, but not 7. If ATG cannot be programmed to perform .10 test and complete it, a precision test is needed. |
| 5, 6, 7 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). |