Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2009002
Status: Active
Facility Name: 3330 Kimball, Inc.
Address: 3330 N. Kimball Ave.
Chicago, IL 60618
County: Cook
Property Parcel: 13-23-407-018-0000
Facility Type: Attended Self-Service/Unattended Self-Service
Owner Type: Private
Green Tag Decal: Z002399
Green Tag Issue Date: 5/29/2024
Green Tag Expiration Date: 12/31/2026

Owner Details

Owner Name: 3330 Kimball Real Estate, Inc.
Owner Address: 515 Alive Drive
Northbrook, IL 60062
Owner Status: Current Owner
Purchase Date: 2/21/2020
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 3/3/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 5/29/2024 12/31/2026

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0040246 3330 Kimball Real Estate, Inc. Current Owner 2/21/2020
U0008379 Kennedy & Kimball Service, Inc. Former Owner 6/20/1989

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00522-2025UPG Upgrade Approved / Issued 5/1/2025 5/1/2025 11/4/2025 Documents

Notice of Violations (Current)

NOV Number: E0020251298 (Pending)    Issue Date: 5/19/2025    Expiration Date: 7/18/2025   

Tanks Violation
1, 2, 3 Annual piping impressed current test not completed. - Retest after repair.
1, 2, 3 Impressed current system failed test or appears non operational. Must repair. - Piping failed impressed current testing by Protanic on May 14, 2025.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
N/A 5/13/2024 Removal Log 00404-2024REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
90-2327 Eligible 1/3/2005 1/24/2005 $10,000
20240381 Eligible 5/29/2024 6/17/2024 $5,000 Letter
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 5/5/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/8/2024 5/8/2025
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/30/2025 4/30/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/30/2025 4/30/2026
Overfill Prev Device Overfill Drop Tube Valve 4/30/2025 4/30/2028
Piping Steel Single Wall Piping N/A N/A
Piping Single Wall STP/Tanktop Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 6/6/2024 6/6/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/30/2025



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 5/5/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/8/2024 5/8/2025
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/30/2025 4/30/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/30/2025 4/30/2026
Overfill Prev Device Overfill Drop Tube Valve 5/5/2025 5/5/2028
Piping Steel Single Wall Piping N/A N/A
Spill Contain Device Double Wall Spill Bucket 5/5/2025 5/5/2028
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/30/2025



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 41 Abandoned Date:
Install Date: 5/5/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 5/8/2024 5/8/2025
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Mechanical Pressurized Line Leak Detection 4/30/2025 4/30/2026
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 450 Plus with CSLD 4/30/2025 4/30/2026
Overfill Prev Device Overfill Drop Tube Valve 4/30/2025 4/30/2028
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 5/8/2024 5/8/2027
Tank Fiberglass Single Wall Owens Corning N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Steel Single Wall Piping Precision Test (Piping) Pass 4/30/2025



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 5/13/2024
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 40 Abandoned Date:
Install Date: 5/5/1984 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Impressed Current Cathodic Protection 6/28/2023 6/28/2024
Corrosion Prot - Tank Impressed Current Cathodic Protection 6/28/2023 6/28/2024
Leak Detect - Piping Gravity Feed N/A N/A
Leak Detect - Tank 110 - 600 gallons Manual Tank Gauging N/A N/A
Overfill Prev Device Less than 25 gallon fills N/A N/A
Piping Steel Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 6/2/2021 6/2/2024
Tank Steel Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Not Installed UDC Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms