Division of Petroleum & Chemical Safety

 

Facility Details

Facility Number: 2008994
Status: Active
Facility Name: Harvey BP, Inc.
Address: 288 W. 147th Street Harvey, IL 60426
County: Cook
Property Parcel: 29-07-301-051
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y000228
Green Tag Issue Date: 1/29/2024
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: First Midwest Bank as Trustee of Trust 21177
Owner Address: 50 W. Jefferson Street Joliet, IL 60432
Owner Status: Current Owner
Purchase Date: 1/18/2012
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 7/11/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 1/29/2024 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0041517 First Midwest Bank as Trustee of Trust 21177 Current Owner 1/18/2012
U0039032 Ahmed, Qasem Former Owner 1/1/2017
U0037063 Sibley Fuel & Mini-Mart, Inc. Former Owner 1/9/2009
U0027042 TGS New Enterprises Limited, LLC Former Owner 3/1/2003
U0034726 Mavi Oil, Inc. Former Owner
U0033514 Dixie Highway Marathon Former Owner
U0010471 Exxon Mobil Oil Corporation Former Owner

Permits (Unexpired)

Click for permit history
Permit Number Type Status OSFM Receive Date Issue Date Expiration Date Documents
00906-2025UPG Upgrade Approved / Issued 7/15/2025 7/15/2025 1/15/2026 Documents

Notice of Violatlions (Current)

NOV Number: E0020251467 (Pending)    Issue Date: 6/6/2025    Expiration Date: 11/30/2025    View NOV Form

Tanks Violations
5 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves are not mounted correctly. (Crossbar is not secure)
5, 6 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves are to low.
7 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves are not mounted correctly. (Crossbar is not secure)
7 Shear valve(s) not properly mounted and/or not at proper height. - Shear valves are to low.

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
89-1856 Eligible 5/18/1994 6/9/1994 $10,000
Pay Tank Fees Online

Tank Information



Tank Number 1

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1989
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 2

Capacity: 10000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1989
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 3

Capacity: 8000 Petroleum Use:
Product: Gasoline CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1989
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 27 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 4

Capacity: 550 Petroleum Use:
Product: Used Oil CERCLA Substance:
Status: Removed CAS Code:
Regulated Status: Federal Removed Date: 10/1/1989
OSFM First Notify Date: 5/5/1986 Abandoned Material:
Current Age: 28 Abandoned Date:
Install Date: Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date:

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date



Tank Number 5

Capacity: 10000 Petroleum Use:
Product: Gasoline - Premium CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/12/2023 9/12/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/9/2024 12/9/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/9/2024 12/9/2025
Overfill Prev Device Ball Float Vent Valve 9/12/2023 9/12/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Single Wall Spill Bucket 9/12/2023 9/12/2026
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/9/2024



Tank Number 6

Capacity: 10000 Petroleum Use: None
Product: Diesel Fuel CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/12/2023 9/12/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/9/2024 12/9/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/9/2024 12/9/2025
Overfill Prev Device Overfill Drop Tube Valve 1/11/2024 1/11/2027
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 1/11/2024 1/11/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/9/2024



Tank Number 7

Capacity: 12000 Petroleum Use:
Product: Gasoline - Regular CERCLA Substance:
Status: Currently in use CAS Code:
Regulated Status: Federal Removed Date:
OSFM First Notify Date: 10/22/1991 Abandoned Material:
Current Age: 35 Abandoned Date:
Install Date: 11/1/1989 Red Tag Issue Date:
Last Used Date: Fee Due: $0.00
Product Date: 11/1/1989

Equipment

Equipment Type Equipment Last Passing Date Test Expire Date
Corrosion Prot - Piping Sacrificial Anode Flex Connector 9/12/2023 9/12/2026
Corrosion Prot - Piping Fiberglass Non-Corrosive N/A N/A
Corrosion Prot - Tank Fiberglass Non-Corrosive N/A N/A
Leak Detect - Piping Electronic Pressurized Line Leak Detection 12/9/2024 12/9/2025
Leak Detect - Tank Automatic Tank Gauging Veeder Root TLS 350 with CSLD 12/9/2024 12/9/2025
Overfill Prev Device Ball Float Vent Valve 9/12/2023 9/12/2026
Piping Fiberglass Single Wall Piping N/A N/A
Piping Not Installed STP/Tanktop Sump N/A N/A
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A
Spill Contain Device Double Wall Spill Bucket 1/11/2024 1/11/2027
Tank Fiberglass Single Wall N/A N/A

Additional Tests

Equipment Type Equipment Test Type Test Result Test Date
Piping Fiberglass Single Wall Piping Precision Test (Piping) Pass 12/9/2024

Dispenser Information



Name\ID 1/2

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 3/4

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 5/6

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 7/8

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A



Name\ID 9/10

Status: Active
Equipment Type Equipment Last Passing Date Test Expire Date
Dispenser Single Wall UDC Sump
Leak Detect - Piping Piping Sump Sensors Not Regulated Not Installed N/A N/A

MFD Motorfuel Dispensing Forms

No Forms Found