Notice of Violations (Current)
NOV Number:
E0020250682
(Pending)
Issue Date:
3/17/2025
Expiration Date:
5/16/2025
View NOV Form
Tanks |
Violation |
Facility |
Facility Operation and Maintenance Plan not completed or available. - Adopt and implement a written operations and maintenance plan, signed by both the owner and either a Class A or Class B Operator designated for the UST facility An Operations & Maintenance template is available at www.sfm.illinois.gov to download and complete O & M template and maintain completed form on site. |
Facility |
Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures plan shall be maintained on site for viewing and reference as necessary (See Operator Training Rules 176.645). The emergency plan template is available on the OSFM website. |
2, 3 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
2, 3 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator green light on panel of Veeder-Root ATG is not functional. Replace as necessary to provide proper operation. |
NOV Number:
E0020250684
(Pending)
Issue Date:
3/17/2025
Expiration Date:
5/16/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. |