Notice of Violations (Current)
NOV Number:
E0020250717
(Pending)
Issue Date:
3/19/2025
Expiration Date:
5/18/2025
View NOV Form
Tanks |
Violation |
Facility |
Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs or dispensers. Perform test, complete form (form is available at www.sfm.illinois.gov) and maintain 2 years on site with other annual testing documentation. |
Facility |
Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and 2 years documentation maintained on site. |
1, 2, 3, 4, 5 |
Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Must maintain 2 years of inspection reports. |
1, 2, 3, 4, 5 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
1, 2, 3, 4, 5 |
Tank monitor does not appear to function properly and requires maintenance. - Indicator light(s) on panel of Veeder-Root ATG is/are not functional. Replace as necessary to provide proper operation. |
NOV Number:
E0020250719
(Pending)
Issue Date:
3/19/2025
Expiration Date:
5/18/2025
View NOV Form
Tanks |
Violation |
Facility |
Fire Extinguishers - Past due for annual testing - Fire extinguishers require annual testing. Have annual testing performed and tag all fire extinguishers accordingly. |
Facility |
Miscellaneous - MISCELLANEOUS |