Notice of Violations (Current)
NOV Number:
E0020232523
(Referred to Legal)
Issue Date:
11/8/2023
Expiration Date:
1/7/2024
View NOV Form
Tanks |
Violation |
2 |
Failed to Empty the Tank to 1" or Less - When placing a tank into out of service it is required to be emptied to 1" or less of fuel.
Current volume 755 gallons (238 gallons of water). |
2 |
Submit Notification Form For Tank Status Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. This form is required to be submitted within 30 days of a tank status change
Place Tank 2 into OUT OF SERVICE |
NOV Number:
E0020240586
(Referred to Legal)
Issue Date:
2/29/2024
Expiration Date:
4/29/2024
View NOV Form
Tanks |
Violation |
1 |
Submit Notification Form For Tank Status Change - The Notification Form is available at https://webapps.sfm.illinois.gov/USTPortal/NotificationForm. Tank 1 needs to be taken out of service. Maged Askur stated that the tank has not been used since Nov. 23rd. 2023. |
NOV Number:
E0020250074
(Referred to Legal)
Issue Date:
1/8/2025
Expiration Date:
3/9/2025
View NOV Form
Tanks |
Violation |
1, 2 |
Remove tank(s) - Single-Walled, Over 30 Years Old and OOS Over One Year - Tanks have not been removed. |
NOV Number:
E0020250645
(Pending)
Issue Date:
3/12/2025
Expiration Date:
5/11/2025
View NOV Form
Tanks |
Violation |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Intercom system not functional; repair/replace as necessary to provide communication at dispensers. Reference 175.210 h) |
NOV Number:
E0020250646
(Pending)
Issue Date:
3/12/2025
Expiration Date:
5/11/2025
View NOV Form
Tanks |
Violation |
Facility |
Missing copies of 30 day Walkthrough Inspection Report. - Only has the last 3 months. |
Facility |
Missing copy of emergency instructions or emergency procedures plan - Form can be found at https://sfm.illinois.gov to download and complete. |
Facility |
Missing list of designated Class A/B & C Operators - Form can be found at https://sfm.illinois.gov to download and complete. |
3 |
Open electrical conduit or junction boxes. - Regular Conduit for ATG. Repair/replaced. |
3, 4 |
Precision line test required. - Does not have passing .1 test. Referance 175.640 a)4)B) |
3, 4 |
Required monthly tank leak test records not available. - Maintain one PASSING report per TANK, per month, from ATG. Reference 175.630 c)2)B) (Only has last 3 months) |
3 |
Shear valve(s) not properly mounted and/or not at proper height. - Not mounted properly. |
3 |
Shear valve(s) not properly mounted and/or not at proper height. - Shear valve to low. |
4 |
Shear valve(s) not properly mounted and/or not at proper height. - Not mounted properly. |
4 |
Shear valve(s) not properly mounted and/or not at proper height. - Shear valve to low. |
3, 4 |
Tank precision test required. - Due to missing monthly tank tapes. |
NOV Number:
E0020250648
(Pending)
Issue Date:
3/12/2025
Expiration Date:
5/11/2025
View NOV Form
Tanks |
Violation |
Facility |
Due to a red tagged tank(s) at this facility, after 60 days from the issuance date of this NOV, in the absence of full compliance, all tanks shall be red tagged |