Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2006986
Status: Active
Facility Name: Circle K #6763
Address: 1851 N. Farnsworth
Aurora, IL 60507
County: Kane
Property Parcel: 15-12-101-005
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y003374
Green Tag Issue Date: 12/20/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: RDK Ventures, LLC
Owner Address: 1120 W. Warner Rd.
Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/24/2025

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 12/20/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures, LLC Current Owner 1/7/2010
U0027449 Equilon Enterprises, LLC Former Owner 1/1/1970
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250708 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
Facility Code complying instruction/warning signs are not properly mounted at each dispenser island - 175.220 a) Minimum signage requires letters shall not be less than 7/8” in height. The top of the sign shall be mounted no higher than 10’ above grade. The wording shall include a minimum of 1) “Warning” 2) “Stop Engine” 3) “No Smoking” 4) “Persons fueling vehicles shall remain with their vehicle, at the nozzle, while fueling is in progress” 5) “It is unlawful and dangerous for anyone to dispense gasoline into unapproved containers”

NOV Number: E0020250710 (Pending)    Issue Date: 3/18/2025    Expiration Date: 5/17/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - Emergency shut off switch needs annual testing performed. OSFM form shall be kept on site.
1, 2, 3 Dispensers - hoses cracked, split or worn and require replacement - Replace main hose.
Facility Facility Operation and Maintenance Plan not updated to new requirements. - Operations and Maintenance Template needs to be updated and kept on site.
1, 2, 3 Line interstitial sensors have been raised and rendered inoperational. - All dispensers Section 175.640 a)2) All new and existing sump sensors must be installed so as to detect liquid per manufacturer's specifications or, if not specified by the manufacturer, at the lowest point in the sump.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual walkthrough needs to be performed. OSFM form shall be completed and kept on site.
Facility Missing copy of emergency instructions or emergency procedures plan - Emergency Procedures Plan needs to be updated and kept on site.
1, 2, 3 Piping interstitial must be open in all sumps - 175.420 b) Unless otherwise required by the manufacturer, the dispenser product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. This is for all sumps.
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Shear valves need annual testing performed. OSFM form shall be completed and kept on site.
1, 2, 3 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. - 175.405 a) 1) A) Spill containment equipment that will prevent release of product to the environment when the transfer hose is detached from the fill pipe (e.g., a spill catch basin). Spill containment equipment shall be maintained in a dry, clean state.

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
96-1868 10/8/1996 Removal Log

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
08-1073 Eligible 10/1/2008 10/29/2008 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 8000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Gasoline - Regular Currently in use Federal $0.00
4 1000 Used Oil Removed Federal $0.00 10/08/1996 - REM
5 1000 Fuel Oil Removed State 10/08/1996 - REM

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active

MFD Motorfuel Dispensing Forms

No Forms Found