Notice of Violations (Current)
NOV Number:
E0020250507
(Referred to Legal)
Issue Date:
2/27/2025
Expiration Date:
4/28/2025
View NOV Form
Tanks |
Violation |
5, 6, 7 |
Piping interstitial must be open in all sumps - Product piping sump jumper tubes shall be removed or the product piping test boots pulled back after testing to allow the interstice to be open to the sump sensors. 175.420 b) (All STPs) |
5 |
Triennial testing for qualifying piping containment sump not completed (Required every 3 years). - Triennial testing for qualifying STP piping containment sump failed test. Repair/replace as necessary to pass retesting of sump. (Regular STP failed test on 12/2/2024) |