Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2006959
Status: Active
Facility Name: 151st & Harlem, LLC
Address: 15100 S. Harlem
Orland Park, IL 60462
County: Cook
Property Parcel: 28-07-300-002-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Y002613
Green Tag Issue Date: 5/11/2023
Green Tag Expiration Date: 12/31/2025

Owner Details

Owner Name: 151st & Harlem, LLC
Owner Address: 15100 S. Harlem
Orland Park, IL 60462
Owner Status: Current Owner
Purchase Date: 8/1/2011
Type of Financial Responsibility: Commercial Insurance
Financial Responsibility Reporting Due Date: 4/13/2026

Motor Fuel Dispensing Permits

MFD Permit Type Issue Date Expiration Date
Self Service 6/6/2023 12/31/2025

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0039080 151st & Harlem, LLC Current Owner 8/1/2011
U0035735 True North Energy, LLC Former Owner 3/8/2010
U0027449 Equilon Enterprises, LLC Former Owner 1/1/1979
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020250481 (Referred to Legal)    Issue Date: 2/25/2025    Expiration Date: 4/26/2025    View NOV Form

Tanks Violation
Facility Annual Emergency Stop Inspection not completed or inspection report not available. - All emergency shutoff switches shall be tested annually to verify they shut down all STPs and dispensers. Form can be found at https://sfm.illinois.gov to download and complete.
Facility Missing copies of Annual Walkthrough Inspection Report. - Annual Walkthrough by a licensed contractor shall be conducted and documentation maintained on site.
Facility Missing list of designated Class A/B & C Operators - Form can be found at https://sfm.illinois.gov to download and complete.
2 Open electrical conduit or junction boxes. - Junction box for ATG is missing the cap. Repair/Replace
1, 2, 3 Shear valve inspection report not completed (Required during Annual Walkthrough Inspection). - Provide documentation that annual testing of all shear valves has been conducted and passed. Go to https://sfm.illinois.gov to print out the Shear Valve inspection form.
1, 2 Verify and test piping sump sensor for positive shutdown - For installations and replacements after September 1, 2010, these sensors must immediately shut off the submersible turbine pump (STP) supplying that line upon detection of a release. (Regular and Premium STP) (Like for like replacement 2011 and 2023)

IEMA Numbers Associated with the Facility

No IEMA Numbers Found

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
03-0358 Eligible 7/2/2003 7/21/2003 $10,000
03-0358 Eligible 10/5/2011 12/2/2011 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline - Regular Currently in use Federal $0.00
2 10000 Gasoline - Premium Currently in use Federal $0.00
3 10000 Diesel Fuel Currently in use Federal $0.00

Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active
11/12 Active

MFD Motorfuel Dispensing Forms