Deficiencies (Current)
NOV Number:
E0020240847
(Pending)
Issue Date:
3/20/2024
Expiration Date:
5/19/2024
View NOV Form
Tanks |
Deficiency |
Facility |
Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable |
NOV Number:
E0020240848
(Pending)
Issue Date:
3/20/2024
Expiration Date:
5/19/2024
View NOV Form
Tanks |
Deficiency |
5, 6, 7 |
Install or replace lockable fill pipe caps. - Need to put locks on the snap caps that are not in a spill bucket. |
5, 6, 7 |
Overfill prevention equipment inspection(s) not completed (Required every 3 years). - Facility has Ball Float vent vavles on all tanks that need to be tested. |
5, 7 |
Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry. |
5 |
Spill prevention equipment device is in disrepair and requires replacement. - Repair/replace Lid. |