Division of Petroleum & Chemical Safety

 
Pay Tank Fees Online Print Detail Page Export to Excel

Facility Details

Facility Number: 2006911
Status: Active
Facility Name: Circle K #6755
Address: 10258 South Kedzie Evergreen Park, IL 60642
County: Cook
Property Parcel: 24-01-202-009-0000
Facility Type: Attended Self-Service Station
Owner Type: Private
Green Tag Decal: Z001299
Green Tag Issue Date: 6/11/2024
Green Tag Expire Date: 12/31/2026
MFD Type: Self Service

Owner Details

Owner Name: RDK Ventures LLC
Owner Address: 1120 W. Warner Rd. Tempe, AZ 85284
Owner Status: Current Owner
Purchase Date: 1/7/2010
Type of Financial Responsibility: Guarantee
Financial Responsibility Reporting Due Date: 10/27/2027

Owner Summary

Click for Facility/Tank Ownership history
Owner Number Owner Name Owner Status Purchase Date
U0035671 RDK Ventures LLC Current Owner 1/7/2010
U0027449 Equilon Enterprises, LLC Former Owner 12/1/1976
U0013849 Shell Oil Products Former Owner 12/31/1967
U0031151 Shell Oil Products US c/o Gilbarco Veeder-Root Former Owner

Permits (Unexpired)

Click for permit history

No Active Permits Found

Notice of Violations (Current)

NOV Number: E0020261620 (Pending)    Issue Date: 6/24/2026    Expiration Date: 8/23/2026    View NOV Form

Tanks Violations
4, 5 Annual leak detection certification not completed (Required annually). - Annual leak detection certification (ATG) failed testing. Repair/replace as necessary. Retesting shall be completed and maintain passing test documentation on site. Failed on 5/18/2026
5 Install or replace lockable fill pipe caps. - Found Permium fill cap off and it will not snap back on the fill adaptor properly. Repair/Replace fill cap. (Low Profile cap)
4, 5 Line interstitial sensors have been raised and rendered inoperational. - Dispenser 3/4 and Premium STP sensors are raised.
4, 5 Spill prevention equipment contains liquid/debris and must be cleared of materials and maintained clean and dry.
4, 5 Tank monitor does not appear to function properly and requires maintenance. - T1 Periodic test fail is in alarm. Repair/Replace to clear alarm.
4, 5 Water in containment with required interstitial sensors - Remove water and repair containments to prevent water ingress. - Dispenser 3/4 and premium STP. Will need to see documentation showing containments have been fixed.

NOV Number: E0020261621 (Pending)    Issue Date: 6/24/2026    Expiration Date: 8/23/2026    View NOV Form

Tanks Violations
Facility Farthest dispenser is greater than 40' and site lacks a communication system or system is inoperable - Communication system is not working. Repair/Replace

IEMA Numbers Associated with the Facility

IEMA Number Inspection Date Inspection Type Permit Number
00-1463 8/3/2000 Removal Log 01213-2000REM

LUST Fund Eligibility and Deductibility Determinations

IEMA Number Status OSFM Received Date OSFM Response Date Deductible Letter
00-1463 Eligible 3/1/2001 3/21/2001 $10,000
Pay Tank Fees Online

Tank Information

Tank Number Capacity Product Status Regulated Status Red Tag Issued Fee Due Abandon/Removal Date
1 10000 Gasoline Removed Federal $0.00 08/03/2000 - REM
2 10000 Gasoline Removed Federal $0.00 08/03/2000 - REM
3 10000 Gasoline Removed Federal $0.00 08/03/2000 - REM
4 20000 Gasoline - Regular Currently in use Federal $0.00
5 12000 Gasoline - Premium Currently in use Federal $0.00


Dispenser Information

Name\ID Status
1/2 Active
3/4 Active
5/6 Active
7/8 Active
9/10 Active


MFD Motorfuel Dispensing Forms

No Forms Found